Si12-308
Control Specification
Function and Control
109
3.16 Additional Function
3.16.1
Connection Pipe Condensation Preventing Function
This control is intended to adjust the electronic expansion valve opening so that the outdoor unit
gas pipe temperature (GDN) be kept below 8°C.
3.16.2
Priority Room Setting
Electronic expansion valves are controlled to provide the unit designated as the priority room
with the capacity of other room units.
(Distribution of capacity: Priority room unit ---
∆
D Max., other room units ---
∆
D -
α
)
Setting method
Turn off the circuit breaker before changing the setting.
Only one room can be set as the priority room.
Control start conditions
Priority room setting is made.
AND
“Powerful” signal from the priority room unit is received.
Note:
The operation mode of the priority room unit has precedence.
Cancellation of control
The control function is canceled when the “Powerful” operation mode is switched off or 20
minutes elapse after “Powerful Operation” started.
3.16.3
Powerful Operation Mode
Compressor operating frequency is increased to P1 Max. (Max. Hz of operating room unit
Σ
S)
and outdoor unit airflow rate is increased.
3.16.4
Voltage Detection Function
Power supply voltage is detected each time equipment operation starts.
C
room
B
room
A
room
Living
room
C
room
B
room
A
room
Living
room
When Inverter
powerful-operation
is selected in the
priority room
Normal
operation
(R1396)
Summary of Contents for Super Multi NX B series
Page 7: ...Si12 308 vi Table of Contents ...
Page 29: ...List of Functions Si12 308 18 List of Functions ...
Page 71: ...Specifications Si12 308 60 Specifications ...
Page 175: ...Instruction Si12 308 164 System Configuration ...
Page 227: ...Check Si12 308 216 Service Diagnosis ...
Page 288: ...Si12 308 Wiring Diagrams Appendix 277 FTXD50BVMC FTXD60 71BVMC ...
Page 299: ...Si12 308 iv Index ...