Field Settings for Outdoor Unit
SiUS341615E
141
Field Settings
2.6.1 List of Setting Mode (Mode 2)
This overview shows the available settings by using the press buttons on the outdoor unit PCB.
No.
∗
1
Item
Description
7 segment
display
Description
7 segment
display
Range
SEG
1
SEG
2
SEG
3
SEG
1
SEG
2
SEG
3
0
COOL/HEAT
selection
Several systems as 1 zone change over
COOL/HEAT:
INDIVIDUAL:
VRV
indoor unit or A-B-C
input set mode.
MASTER: System is the COOL/HEAT
master unit.
SLAVE: System is not a COOL/HEAT
master.
2
.
0
0
Individual
0
Unified master
1
Unified slave
2
1
COOL/HEAT
unified address
Used to make address setting for unified
cooling/heating operation.
2
.
0
1
0
0
Address
31
3
1
2
Low noise/
demand address
Used to make address setting for low noise/
demand operation.
2
.
0
2
0
0
Address
31
3
1
5
Indoor fan forced
H
Used to force the fan of indoor unit to H tap.
2
.
0
5
Normal operation
0
Indoor fan H
1
6
Forced
thermostat
Used to force all indoor units to operate
forced thermostat ON.
2
.
0
6
Normal operation
0
Forced thermostat ON
1
8
Te setting
Used to make setting of targeted
evaporating temperature for cooling
operation.
2
.
0
8
Auto
(6-11°C) (42.8-51.8°F)
0
Standard: 6°C (42.8°F)
2
High sensible: 7°C (44.6°F)
3
High sensible: 8°C (46.4°F)
4
High sensible: 9°C (48.2°F)
5
High sensible: 10°C (50.0°F)
6
High sensible: 11°C (51.8°F)
7
9
Tc setting
Used to make setting of targeted
condensing temperature for heating
operation.
2
.
0
9
Auto
(38-46°C)
(100.4-114.8°F)
0
Low: 41°C (105.8°F)
1
Normal: 43°C (109.4°F)
3
High: 46°C (114.8°F)
6
12
External low
noise setting/
demand setting
Used to receive external low noise or
demand signal.
2
.
1
2
Input LNO/DE :
NO
0
: YES
1
13
AIRNET address Used to set address of AIRNET
2
.
1
3
0
0
Address
63
6
3
16
Heat pump
lockout 1
Used for heat pump lockout
2
.
1
6
OFF
0
ON
1
18
High ESP setting
FAN
Fan high static pressure setting
2
.
1
8
OFF
0
ON
1
20
Additional
refrigerant
charge
Used to perform additional refrigerant
charging operation (compressor operation).
2
.
2
0
Refrigerant charging
OFF
0
ON
1
21
Refrigerant
recovery and
vacuuming
Used to set the system to refrigerant
recovery mode (without compressor run).
2
.
2
1
Refrigerant recovery
OFF
0
ON
1
22
Automatic night-
time low noise
operation
Automatic night-time low noise operation.
Time for the operation is subject to the start
and end time settings.
2
.
2
2
OFF
0
Level 1
1
Level 2
2
Level 3
3
25
External low
noise level
Low noise level when the external low noise
signal is input at option DTA104A61.
2
.
2
5
Level 1
1
Level 2
2
Level 3
3
~
~
~
~
~
~
~
Summary of Contents for RXYQ-TA Series
Page 1: ...Service Manual SiUS341615E RXYQ72 408TAYDU RXYQ72 408TATJU Heat Pump 60 Hz...
Page 321: ...SiUS341615E Wiring Diagrams Appendix 308 RXYQ96 120TAYDU 2D106439A...
Page 322: ...Wiring Diagrams SiUS341615E 309 Appendix RXYQ144 168TAYDU 2D106440A...
Page 323: ...SiUS341615E Wiring Diagrams Appendix 310 RXYQ72TATJU 3D106435A...
Page 324: ...Wiring Diagrams SiUS341615E 311 Appendix RXYQ96 120TATJU 2D106436A...
Page 325: ...SiUS341615E Wiring Diagrams Appendix 312 RXYQ144 168TATJU 2D106437A...
Page 335: ...SiUS341615E Wiring Diagrams Appendix 322 VAM1200GVJU 3D073270C...
Page 336: ...Revision History Month Year Version Revised contents 02 2017 SiUS341615E First edition...