Troubleshooting by Error Code
SiUS341615E
251
Service Diagnosis
YES
Recheck for the compressor and the
refrigerant system.
NO
Replace the inverter PCB.
RXYQ72-120TA: A3P
RXYQ144/168TA: A3P, A6P
NO
YES
NO
There is
wiring disconnection in
the compressor.
Replace the inverter compressor.
YES
Is the
insulation
resistance of the
relevant compressor
100 k
Ω
or more?
Refrigerant is
melting (No power
applied for a period of 6
hours or more)
Replace the inverter compressor.
NO
Eliminate the melting state of
refrigerant.
YES
CHECK 4
Is the power
transistor normal?
A
CHECK 4