Refrigerant Circuit
SiUS341615E
17
Refrigerant Circuit
1.3
Outdoor-Air Processing Unit
Note:
∗
1. SH control: Superheated control of heat exchanger outlet
∗
2. SC control: Subcooling control of heat exchanger outlet
No. in
piping
diagram
Electric
symbol
Name
Function
(1)
Y1E
Electronic expansion valve
Used to control the flow rate of refrigerant, and make the
SH control (
∗
1) while in cooling.
(2)
Y1S
Solenoid valve
Used to bypass hot gas while in heating with thermostat
OFF. Closed while in cooling.
(3)
—
Capillary tube
Used to reduce pressure from high to low in bypassing hot
gas.
(4)
R1T
Suction air thermistor
Used to turn ON or OFF the thermostat.
(5)
R2T
Liquid pipe thermistor
Used to control the opening degree of electronic expansion
valve under the SC control (
∗
2).
(6)
R3T
Gas pipe thermistor
Used to control the opening degree of electronic expansion
valve under the SH control.
(7)
R4T
Discharge air thermistor
Used to control the electronic expansion valve opening and
thermostat ON/OFF so as to keep the discharge air
temperature at the set temperature.
C: 4D018650D
Heat exchanger
Distributor
Fan
Filter
Filter
Filter
Electronic
expansion valve
Capillary
tube
Solenoid
valve
Check
valve
Gas pipe
connection port
Liquid pipe
connection port
(5)
(7)
(6)
(3)
(2)
(1)
(4)
Summary of Contents for RXYQ-TA Series
Page 1: ...Service Manual SiUS341615E RXYQ72 408TAYDU RXYQ72 408TATJU Heat Pump 60 Hz...
Page 321: ...SiUS341615E Wiring Diagrams Appendix 308 RXYQ96 120TAYDU 2D106439A...
Page 322: ...Wiring Diagrams SiUS341615E 309 Appendix RXYQ144 168TAYDU 2D106440A...
Page 323: ...SiUS341615E Wiring Diagrams Appendix 310 RXYQ72TATJU 3D106435A...
Page 324: ...Wiring Diagrams SiUS341615E 311 Appendix RXYQ96 120TATJU 2D106436A...
Page 325: ...SiUS341615E Wiring Diagrams Appendix 312 RXYQ144 168TATJU 2D106437A...
Page 335: ...SiUS341615E Wiring Diagrams Appendix 322 VAM1200GVJU 3D073270C...
Page 336: ...Revision History Month Year Version Revised contents 02 2017 SiUS341615E First edition...