SiUS341615E
Basic Control
Functions and Control
60
5.6
Step Control of Outdoor Fans
Used to control the revolutions of outdoor unit fans in the steps listed in table below, according to condition
changes.
Note:
1. Figures listed above are all those controlled while in standard mode, which vary when the
system is set to high static pressure or capacity priority mode.
Step
Fan revolutions (rpm)
RXYQ72TA
RXYQ96/120TA
RXYQ144/168TA
M1F
M2F
M1F
M2F
0
0
0
0
0
0
1
350
360
0
380
0
2
370
470
0
470
0
3
400
570
0
570
0
4
460
360
360
380
380
5
560
550
520
550
520
6
710
865
665
865
665
7Y
750
940
910
940
910
7X
Cooling: 821
Heating: 800
963
933
1136
1106
8
Cooling: 821
Heating: 800
1097
1067
1360
1180