Check
SiUS341615E
291
Service Diagnosis
4. Check
4.1
High Pressure Check
Referring to the Fault Tree Analysis (FTA) shown below, probe the defective points.
Note:
∗
1. In cooling, it is normal if the outdoor unit electronic expansion valve (main) is fully open.
∗
2. In heating, the indoor unit electronic expansion valve is used for “subcooling degree control”.
CHECK 1
Short circuit
Rise in high
pressure
Local
pressure
rise
High pipe
resistance
Stop valve closed
Bent or crashed pipe
Clogging of foreign
materials
In cooling
If the outdoor unit electronic
expansion valve is throttled:
(
∗
1)
Defective outdoor
unit electronic
expansion valve
Defective indoor
unit electronic
expansion valve
Defective valve coil
Defective valve body
A temperature difference in excess of 10
°
C
between the inlet and the outlet is deemed to be abnormal.
Defective
control
Defective high pressure sensor
Defective outdoor
unit main PCB
Defective
high pressure
control
Defective valve coil
Defective valve body
In heating
If the indoor unit electronic
expansion valve excessively
throttled:
(
∗
2)
Defective
control
Defective high pressure sensor
Defective indoor unit
liquid pipe thermistor
Defective outdoor
unit main PCB
In cooling
High suction
air
temperature
of the
condenser
In heating
High suction air
temperature of
outdoor unit
Short circuit
High outdoor air
temperature
High suction
air temperature
of indoor unit
High room
temperature
Defective suction air thermistor of indoor unit
High suction air temperature of outdoor unit
Defective outdoor air thermistor of outdoor unit
Degradation
in condensing
capacity
Dirty condenser
Mixing of non-condensable gas
Decreased
airflow rate
Decreased
fan
output
Defective fan
motor
Defective
outdoor unit main
PCB (Including
capacity setting)
High
airflow
passage
resistance
Dirty filter
Obstacle
Excessive refrigerant charging
Improper model selection In heating
←
Check to be sure the stop valve is open.
←
Conduct visual checks for pipe conditions.
←
Is there any temperature difference caused before
and after the filter or branch pipe?
←
Are the coil resistance and insulation normal?
←
Are the electrical characteristics normal?
←
Is the pressure value checked with the Service Checker
corresponding to the measurement value of the pressure sensor?
←
Are the coil resistance and insulation
normal?
←
Are the electrical characteristics normal?
←
Is the connector properly connected?
Are the thermistor resistance characteristics normal?
←
Is the pressure value checked with the Service
Checker corresponding to the measurement value of
the pressure sensor?
←
Is the suction air temperature less than 43
°
C (109˚F)?
←
Is the outdoor air temperature less than 43
°
C (109˚F)?
←
Is the suction air temperature less than 27
°
C (80.6˚F)?
←
Is the room temperature less than 27
°
C (80.6˚F)?
←
Is the connector properly connected?
Are the thermistor resistance characteristics normal?
←
Is the outdoor air temperature less than 16
°
CWB (60.8
°
FWB)?
←
Is the connector properly connected?
Are the thermistor resistance characteristics normal?
←
Is the heat exchanger clogged? (In cooling)
←
Is air or else mixed in the refrigerant system?
←
Can the fan motor be rotated with hands?
Are the motor coil resistance and
insulation normal?
←
If a spare PCB is mounted, is the capacity
setting properly made?
←
Is the air filter clogged?
←
Is there any obstacle in the airflow passage?
←
Refer to
←
Is the indoor unit too small compared to
the large-sized outdoor unit?
CHECK 6
Summary of Contents for RXYQ-TA Series
Page 1: ...Service Manual SiUS341615E RXYQ72 408TAYDU RXYQ72 408TATJU Heat Pump 60 Hz...
Page 321: ...SiUS341615E Wiring Diagrams Appendix 308 RXYQ96 120TAYDU 2D106439A...
Page 322: ...Wiring Diagrams SiUS341615E 309 Appendix RXYQ144 168TAYDU 2D106440A...
Page 323: ...SiUS341615E Wiring Diagrams Appendix 310 RXYQ72TATJU 3D106435A...
Page 324: ...Wiring Diagrams SiUS341615E 311 Appendix RXYQ96 120TATJU 2D106436A...
Page 325: ...SiUS341615E Wiring Diagrams Appendix 312 RXYQ144 168TATJU 2D106437A...
Page 335: ...SiUS341615E Wiring Diagrams Appendix 322 VAM1200GVJU 3D073270C...
Page 336: ...Revision History Month Year Version Revised contents 02 2017 SiUS341615E First edition...