SiUS341615E
Field Setting from Remote Controller
Field Settings
116
1.4.3 Outdoor-Air Processing Unit - Field Setting (Remote Controller)
: Factory setting
1.4.4 Setting of Operation Control Mode from Remote Controller
(Field Setting)
The operation control mode is compatible with a variety of controls and operations by limiting the functions of the
operation remote controller. Furthermore, operations such as remote controller ON/OFF can be limited in
accordance with the combination conditions. (Refer to information in the next page.)
Central remote controller is normally available for operations. (Except when centralized monitor is connected)
1.4.5 Contents of Control Modes
20 modes consisting of combinations of the following 5 operation modes with temperature and operation mode
setting by remote controller can be set and displayed by operation modes 0 through 19.
ON/OFF control impossible by remote controller
Used when you want to turn ON/OFF by central remote controller only.
(Cannot be turned ON/OFF by remote controller.)
OFF control only possible by remote controller
Used when you want to turn ON by central remote controller only, and OFF by remote controller only.
Centralized
Used when you want to turn ON by central remote controller only, and turn ON/OFF freely by remote
controller during set time.
Individual
Used when you want to turn ON/OFF by both central remote controller and remote controller.
Timer operation possible by remote controller
Used when you want to turn ON/OFF by remote controller during set time and you do not want to start
operation by central remote controller when time of system start is programmed.
Mode
No.
First
Code
No.
Setting Contents
Second Code No.
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
10
(20)
0
Filter
contamination
2500hr
1250hr
—
—
—
—
—
—
—
—
—
—
—
—
—
3
Display time to
clean air filter
calculation
Display
No
display
—
—
—
—
—
—
—
—
—
—
—
—
—
12
(22)
1
External ON/OFF
input
Forced
OFF
ON/OFF
control
—
—
—
—
—
—
—
—
—
—
—
—
—
5
Power failure
automatic reset
Not
equipped
Equipped
—
—
—
—
—
—
—
—
—
—
—
—
—
14
(24)
3
Discharge
pipe
temperature
(cooling)
°C
13
14
15
16
17
18
19
20
21
22
23
24
25
+
25
+
25
+
°F
55.4
57.2
59
60.8 62.6 64.4 66.2
68
69.8 71.6 73.4 75.2
77
+
77
+
77
+
4
Discharge
pipe
temperature
(heating)
°C
18
19
20
21
22
23
24
25
26
27
28
29
30
+
30
+
30
+
°F
64.4
66.2
68
69.8 71.6 73.4 75.2
77
78.8 80.6 82.4 84.2
86
+
86
+
86
+
Summary of Contents for RXYQ-TA Series
Page 1: ...Service Manual SiUS341615E RXYQ72 408TAYDU RXYQ72 408TATJU Heat Pump 60 Hz...
Page 321: ...SiUS341615E Wiring Diagrams Appendix 308 RXYQ96 120TAYDU 2D106439A...
Page 322: ...Wiring Diagrams SiUS341615E 309 Appendix RXYQ144 168TAYDU 2D106440A...
Page 323: ...SiUS341615E Wiring Diagrams Appendix 310 RXYQ72TATJU 3D106435A...
Page 324: ...Wiring Diagrams SiUS341615E 311 Appendix RXYQ96 120TATJU 2D106436A...
Page 325: ...SiUS341615E Wiring Diagrams Appendix 312 RXYQ144 168TATJU 2D106437A...
Page 335: ...SiUS341615E Wiring Diagrams Appendix 322 VAM1200GVJU 3D073270C...
Page 336: ...Revision History Month Year Version Revised contents 02 2017 SiUS341615E First edition...