SiUS341615E
Outline of Control (Indoor Unit)
Functions and Control
74
8.2.2 With Optional Infrared Floor Sensor
The relationship between remote controller set temperature and control target temperature is
described below.
•
The temperature difference for cooling
⇔
heating mode switching is 5°C (9°F).
•
When using the floor temperature as the control target, the remote controller set temperature is
equal to the actual control target temperature in heating operation.
•
The above also applies to automatic operation.
When setting the suction air thermistor (Default setting)
When using the remote controller thermistor (Field setting is required)
Examples are given to illustrate a control target temperature that satisfies the remote controller set
temperature.
Regarding control target temperature
When using the infrared floor sensor, the temperature around people will be treated as the control
target temperature for operation.
What is the temperature around people?
The temperature around people refers to the temperature of the living space, obtained from the
temperature around the ceiling and the temperature underfoot. The temperature is calculated using
the detected values of the suction air thermistor and the infrared floor sensor.
It is difficult to use only suction air temperature control for underfoot air conditioning.
˚C
Remote controller set temperature
Control target temperature
Remote controller set temperature
Control target temperature
Cooling
Heating
˚F
Temperature
Remote controller set temperature
Control target temperature
Remote controller set temperature
Control target temperature
Cooling
Heating
˚C
˚F
Temperature
Summary of Contents for RXYQ-TA Series
Page 1: ...Service Manual SiUS341615E RXYQ72 408TAYDU RXYQ72 408TATJU Heat Pump 60 Hz...
Page 321: ...SiUS341615E Wiring Diagrams Appendix 308 RXYQ96 120TAYDU 2D106439A...
Page 322: ...Wiring Diagrams SiUS341615E 309 Appendix RXYQ144 168TAYDU 2D106440A...
Page 323: ...SiUS341615E Wiring Diagrams Appendix 310 RXYQ72TATJU 3D106435A...
Page 324: ...Wiring Diagrams SiUS341615E 311 Appendix RXYQ96 120TATJU 2D106436A...
Page 325: ...SiUS341615E Wiring Diagrams Appendix 312 RXYQ144 168TATJU 2D106437A...
Page 335: ...SiUS341615E Wiring Diagrams Appendix 322 VAM1200GVJU 3D073270C...
Page 336: ...Revision History Month Year Version Revised contents 02 2017 SiUS341615E First edition...