Troubleshooting by Error Code
Service Diagnosis
174
3. Troubleshooting by Error Code
3.1
External Protection Device Abnormality
3.1.1 External Protection Device Abnormality (All Indoor Unit Models)
Error Code
A0
Applicable
Models
All indoor unit models
Method of Error
Detection
Detect open or short circuit between external input terminals in indoor unit.
Error Decision
Conditions
When an open circuit occurs between external input terminals with the remote controller set to
"external ON/OFF terminal".
Supposed
Causes
Actuation of external protection device
Improper field setting
Defective indoor unit PCB
Troubleshooting
ON/OFF
input from
outside (mode No.
12, first code No. 1) has
been set to external protection
device input (second
code No. 03) by
remote
controller.
Check the setting state of the
external ON/OFF input by
remote controller.
Ex
ternal
protection device
is connected to T1 and T2
of the indoor unit
terminal.
Replace the indoor unit main
PCB (A1P).
Actuation of external protection
device.
Change the second code No. to
01
or
02
.
YES
NO
NO
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for RXYQ-TA Series
Page 1: ...Service Manual SiUS341615E RXYQ72 408TAYDU RXYQ72 408TATJU Heat Pump 60 Hz...
Page 321: ...SiUS341615E Wiring Diagrams Appendix 308 RXYQ96 120TAYDU 2D106439A...
Page 322: ...Wiring Diagrams SiUS341615E 309 Appendix RXYQ144 168TAYDU 2D106440A...
Page 323: ...SiUS341615E Wiring Diagrams Appendix 310 RXYQ72TATJU 3D106435A...
Page 324: ...Wiring Diagrams SiUS341615E 311 Appendix RXYQ96 120TATJU 2D106436A...
Page 325: ...SiUS341615E Wiring Diagrams Appendix 312 RXYQ144 168TATJU 2D106437A...
Page 335: ...SiUS341615E Wiring Diagrams Appendix 322 VAM1200GVJU 3D073270C...
Page 336: ...Revision History Month Year Version Revised contents 02 2017 SiUS341615E First edition...