Troubleshooting by Error Code
SiUS341615E
237
Service Diagnosis
3.41 High Pressure Sensor Abnormality
Error Code
JA
Applicable
Models
All outdoor unit models
Method of Error
Detection
Detect according to temperature detected with the high pressure sensor.
Error Decision
Conditions
The high pressure sensor is short circuit or open circuit.
(Pressure range: 0-4.3 MPa (0-624 psi))
Supposed
Causes
Defective high pressure sensor
Connection of low pressure sensor in mistake for high pressure sensor
Defective outdoor unit main PCB
Defective connection of high pressure sensor