Outline of Control (Indoor Unit)
SiUS341615E
73
Functions and Control
8.2
Set Temperature and Control Temperature
8.2.1 Without Optional Infrared Floor Sensor
The relationship between remote controller set temperature and control target temperature is
described below.
•
When the suction air thermistor is used for controlling (Default), the control target temperature is
determined as follows to prevent insufficient heating in heating operation.
Control target temperature: remote controller displayed tempe 2°C (3.6°F).
•
The temperature difference for cooling
⇔
heating mode switching is 5°C (9°F).
•
The above also applies to automatic operation.
When setting the suction air thermistor (Default setting)
When using the remote controller thermistor (Field setting is required)
Examples are given to illustrate a control target temperature that satisfies the remote controller set
temperature.
Remote controller set temperature
Control target temperature
Remote controller set temperature
Control target temperature
˚C
Cooling
Heating
˚F
Temperature
Remote controller set temperature
Control target temperature
Remote controller set temperature
Control target temperature
˚C
Cooling
Heating
˚F
Temperature
Summary of Contents for RXYQ-TA Series
Page 1: ...Service Manual SiUS341615E RXYQ72 408TAYDU RXYQ72 408TATJU Heat Pump 60 Hz...
Page 321: ...SiUS341615E Wiring Diagrams Appendix 308 RXYQ96 120TAYDU 2D106439A...
Page 322: ...Wiring Diagrams SiUS341615E 309 Appendix RXYQ144 168TAYDU 2D106440A...
Page 323: ...SiUS341615E Wiring Diagrams Appendix 310 RXYQ72TATJU 3D106435A...
Page 324: ...Wiring Diagrams SiUS341615E 311 Appendix RXYQ96 120TATJU 2D106436A...
Page 325: ...SiUS341615E Wiring Diagrams Appendix 312 RXYQ144 168TATJU 2D106437A...
Page 335: ...SiUS341615E Wiring Diagrams Appendix 322 VAM1200GVJU 3D073270C...
Page 336: ...Revision History Month Year Version Revised contents 02 2017 SiUS341615E First edition...