Troubleshooting by Error Code
SiUS341615E
289
Service Diagnosis
3.68 System Abnormality, Refrigerant System Address
Undefined
Error Code
UH
Applicable
Models
All indoor unit models
All outdoor unit models
Method of Error
Detection
Detect an indoor unit with no auto address setting.
Error Decision
Conditions
The error decision is made as soon as the abnormality aforementioned is detected.
Supposed
Causes
Improper connection of transmission wiring between indoor-outdoor units and outdoor-outdoor
units
Defective indoor unit PCB
Defective outdoor unit PCB