Troubleshooting by Error Code
SiUS341615E
223
Service Diagnosis
3.33 Outdoor Fan Motor Abnormality
Error Code
E7
Applicable
Models
All outdoor unit models
Method of Error
Detection
Detect according to the value of current flowing through the inverter PCB (or fan PCB in case of
Fan Motor 2).
Detect error of the fan motor system according to the fan revolutions detected by the hall IC
during the fan motor runs.
Error Decision
Conditions
Overcurrent is detected from the inverter PCB or the fan PCB (Detecting overcurrent 4 times will
shut down the system).
The fan revolutions fall below a given level for a period of 6 seconds while in fan motor rotation
mode (Detecting shortage of revolutions will shut down the system).
Supposed
Causes
Fan motor failure
Neglect to connect or defective connection of harness/connector between the fan motor and the
PCB
Fan does not rotate due to foreign matter caught in it.
Clearing condition: fan motor performs normal operation for a period of 5 minutes
Summary of Contents for RXYQ-TA Series
Page 1: ...Service Manual SiUS341615E RXYQ72 408TAYDU RXYQ72 408TATJU Heat Pump 60 Hz...
Page 321: ...SiUS341615E Wiring Diagrams Appendix 308 RXYQ96 120TAYDU 2D106439A...
Page 322: ...Wiring Diagrams SiUS341615E 309 Appendix RXYQ144 168TAYDU 2D106440A...
Page 323: ...SiUS341615E Wiring Diagrams Appendix 310 RXYQ72TATJU 3D106435A...
Page 324: ...Wiring Diagrams SiUS341615E 311 Appendix RXYQ96 120TATJU 2D106436A...
Page 325: ...SiUS341615E Wiring Diagrams Appendix 312 RXYQ144 168TATJU 2D106437A...
Page 335: ...SiUS341615E Wiring Diagrams Appendix 322 VAM1200GVJU 3D073270C...
Page 336: ...Revision History Month Year Version Revised contents 02 2017 SiUS341615E First edition...