Service Diagnosis
4.10 Broken Wire Check of the Relay Wires
1. Procedure for checking outdoor-outdoor unit transmission wiring for broken wires
On the system shown below, turn OFF the power supply to all equipment, short circuit between
the outdoor-outdoor unit terminal F1 and F2 in the "Outdoor Unit A" that is farthest from the
central remote controller, and then conduct continuity checks between the transmission wiring
terminal blocks F1 and F2 of the central remote controller using a multimeter. If there is
continuity between the said terminal blocks, the outdoor-outdoor unit transmission wiring has no
broken wires in it.
If there is no continuity, the transmission wiring may have broken wires. With the outdoor-
outdoor unit terminal of the "Outdoor Unit A" short circuited, conduct continuity checks between
the transmission wiring terminal blocks F1 and F2 of the unified ON/OFF controller. If there is no
continuity as well, conduct continuity checks between the outdoor-outdoor unit terminal of the
"Outdoor Unit E", between the outdoor-outdoor unit terminal of the "Outdoor Unit D", between
the outdoor-outdoor unit terminal of the "Outdoor Unit C", … in the order described, thus
identifying the place with continuity.
If the place with continuity can be identified, there may be broken wires in places before the said
place with continuity.
2. Procedure for checking indoor-outdoor unit transmission wiring for broken wires (for checking
the indoor-outdoor unit transmission wiring of the "Outdoor Unit C" for broken wires)
Turn OFF the power supply to all equipment, short circuit between the indoor-outdoor unit
terminal F1 and F2 in the "Outdoor Unit C, and then conduct continuity checks between the
transmission wirings F1 and F2 of the "Indoor Unit a" that is farthest from the "Outdoor Unit C"
using a multimeter. If there is continuity between the said transmission wirings, the indoor-
outdoor unit transmission wiring has no broken wires in it.
If there is no continuity, the transmission wiring may have broken wires. With the indoor-outdoor
unit terminal of the "Outdoor Unit C" short circuited, identify the place with continuity in the
transmission wiring of the "Indoor Unit b", transmission wiring of the "Indoor Unit c", and
transmission wiring of the "Indoor Unit d" in the order described.
If the place with continuity can be identified, there may be broken wires in places before the said
place with continuity.
CHECK 15
Short circuit
between the
outdoor-outdoor
unit terminal
parts.
Outdoor-outdoor Unit
Transmission Wiring
Check the transmission
wiring for continuity.
If there is continuity, the
indoor-outdoor unit
transmission has no
broken wires in it.
Indoor-outdoor Unit
Transmission Wiring
Short circuit between
the indoor-outdoor unit
terminal parts.
Check the transmission
wiring for continuity.
If there is continuity, the
outdoor-outdoor unit
transmission has no broken
wires in it.
Unified ON/OFF controller
Central remote controller
Summary of Contents for RXYQ-TA Series
Page 1: ...Service Manual SiUS341615E RXYQ72 408TAYDU RXYQ72 408TATJU Heat Pump 60 Hz...
Page 321: ...SiUS341615E Wiring Diagrams Appendix 308 RXYQ96 120TAYDU 2D106439A...
Page 322: ...Wiring Diagrams SiUS341615E 309 Appendix RXYQ144 168TAYDU 2D106440A...
Page 323: ...SiUS341615E Wiring Diagrams Appendix 310 RXYQ72TATJU 3D106435A...
Page 324: ...Wiring Diagrams SiUS341615E 311 Appendix RXYQ96 120TATJU 2D106436A...
Page 325: ...SiUS341615E Wiring Diagrams Appendix 312 RXYQ144 168TATJU 2D106437A...
Page 335: ...SiUS341615E Wiring Diagrams Appendix 322 VAM1200GVJU 3D073270C...
Page 336: ...Revision History Month Year Version Revised contents 02 2017 SiUS341615E First edition...