Troubleshooting by Error Code
SiUS341615E
235
Service Diagnosis
3.40 Thermistor Abnormality
Error Code
H9, J3, J5, J6, J7, J8, J9
Applicable
Models
All outdoor unit models
Method of Error
Detection
Detect according to temperature detected with individual thermistors.
Error Decision
Conditions
The system is in operation and the thermistor causes wiring disconnection or short circuit in it.
Supposed
Causes
Defective connection of thermistor
Defective thermistor
Defective outdoor unit PCB
Troubleshooting
Thermistor is
connected to the
connector.
Replace the outdoor unit PCB.
Connect the connector and turn
ON again.
NO
NO
Replace the thermistor (
∗
1).
YES
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Resistance
is normal when
measured after
disconnecting the
thermistor from the
outdoor unit PCB.
CHECK 11
(1.8 k
Ω
to
800 k
Ω
)
Summary of Contents for RXYQ-TA Series
Page 1: ...Service Manual SiUS341615E RXYQ72 408TAYDU RXYQ72 408TATJU Heat Pump 60 Hz...
Page 321: ...SiUS341615E Wiring Diagrams Appendix 308 RXYQ96 120TAYDU 2D106439A...
Page 322: ...Wiring Diagrams SiUS341615E 309 Appendix RXYQ144 168TAYDU 2D106440A...
Page 323: ...SiUS341615E Wiring Diagrams Appendix 310 RXYQ72TATJU 3D106435A...
Page 324: ...Wiring Diagrams SiUS341615E 311 Appendix RXYQ96 120TATJU 2D106436A...
Page 325: ...SiUS341615E Wiring Diagrams Appendix 312 RXYQ144 168TATJU 2D106437A...
Page 335: ...SiUS341615E Wiring Diagrams Appendix 322 VAM1200GVJU 3D073270C...
Page 336: ...Revision History Month Year Version Revised contents 02 2017 SiUS341615E First edition...