SiUS371614E
Protection Control
Functions and Control
76
6.3
Discharge Pipe Protection Control
This discharge pipe protection control is used to protect the compressor internal temperature
against an error or transient increase of discharge pipe temperature.
Normal Operation
3-step down
9-step up
9-step down
3-step up
21-step down
After 30 seconds
After 20 seconds
After 20 seconds
After 30 seconds
HTdi > 115˚C
(239˚F)
HTdi > 130˚C
(266˚F)
HTdi < 105˚C
(221˚F)
HTdi < 110˚C
(230˚F)
HTdi > 115˚C
(239˚F)
HTdi > 120˚C
(248˚F)
HTdi > 125˚C
(257˚F)
Compressor step: 1
After 20 seconds
HTdi > 135˚C (275˚F)
HTdi > 120˚C (248˚F)
continues for 10 minutes
OR
HTdi: Value of inverter compressor
discharge pipe temperature
(Tdi) compensated with
outdoor air temperature
Upper limit compressor step:
max (Max. Step)
Current
step
maintained
Discharge pipe temperature standby
(3 times within 100 minutes)
Abnormal stop
(
F3
is displayed)
Discharge pipe temperature
standby
(2 times within 100 minutes)
After 30
seconds
Summary of Contents for REYQ-TA Series
Page 1: ...Service Manual SiUS371614E REYQ72 456TAYDU REYQ72 456TATJU Heat Recovery 60 Hz...
Page 304: ...Wiring Diagrams SiUS371614E 291 Appendix REYQ96 120TAYDU 2D106425A...
Page 305: ...SiUS371614E Wiring Diagrams Appendix 292 REYQ144 168TAYDU 2D106426A...
Page 306: ...Wiring Diagrams SiUS371614E 293 Appendix REYQ72TATJU 3D106421A...
Page 307: ...SiUS371614E Wiring Diagrams Appendix 294 REYQ96 120TATJU 2D106422A...
Page 308: ...Wiring Diagrams SiUS371614E 295 Appendix REYQ144 168TATJU 2D106423A...
Page 318: ...Wiring Diagrams SiUS371614E 305 Appendix VAM1200GVJU 3D073270C...
Page 320: ...Wiring Diagrams SiUS371614E 307 Appendix 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B...
Page 321: ...SiUS371614E Wiring Diagrams Appendix 308 BS6 8Q54TVJ 2D089122B...
Page 322: ...Wiring Diagrams SiUS371614E 309 Appendix BS10 12Q54TVJ 2D089121B...
Page 323: ...Revision History Month Year Version Revised contents 02 2017 SiUS371614E First edition...