Field Setting from Outdoor Unit
SiUS371614E
141
Field Settings
[1-5]:
shows the current Te target parameter position.
[1-6]:
shows the current Tc target parameter position.
[1-10]: shows the total number of connected indoor units.
It can be convenient to check if the total number of indoor units which are installed match the total
number of indoor units which are recognized by the system. In case there is a mismatch, It is advised to
check the communication wiring path between outdoor and indoor units (F1/F2 communication line).
[1-13]: shows the total number of connected outdoor units (in case of multiple outdoor system).
It can be convenient to check if the total number of outdoor units which are installed matches the total
number of outdoor units which are recognized by the system. In case there is a mismatch, It is advised to
check the communication wiring path between outdoor and outdoor units (Q1/Q2 communication line).
[1-17]: shows the latest error code.
[1-18]: shows the error code which occurred 1 time before current error code.
[1-19]: shows the error code which occurred 2 time before current error code.
When the latest error codes were reset by accident on an indoor unit user interface, they can be checked
again through this monitoring settings.
[1-40]: shows the current cooling comfort setting.
[1-41]: shows the current heating comfort setting.
2.4.2 Mode 2
Mode 2 is used to change the field settings of the system. Consulting the current field setting value and changing
the current field setting value is possible.
In general, normal operation can be resumed without special intervention after changing field settings.
Some field settings are used for special operation (e.g., 1 time operation, recovery/vacuuming setting, manual
adding refrigerant setting, etc.). In such a case, it is required to abort the special operation before normal
operation can restart. It will be indicated in below explanations.
[2-8]:
Te target temperature during cooling operation
Value
[2-8]
Te target
0 (default)
Auto
1
3°C (37.4°F)
2
6°C (42.8°F)
3
7°C (44.6°F)
4
8°C (46.4°F)
5
9°C (48.2°F)
6
10°C (50°F)
7
11°C (51.8°F)
Summary of Contents for REYQ-TA Series
Page 1: ...Service Manual SiUS371614E REYQ72 456TAYDU REYQ72 456TATJU Heat Recovery 60 Hz...
Page 304: ...Wiring Diagrams SiUS371614E 291 Appendix REYQ96 120TAYDU 2D106425A...
Page 305: ...SiUS371614E Wiring Diagrams Appendix 292 REYQ144 168TAYDU 2D106426A...
Page 306: ...Wiring Diagrams SiUS371614E 293 Appendix REYQ72TATJU 3D106421A...
Page 307: ...SiUS371614E Wiring Diagrams Appendix 294 REYQ96 120TATJU 2D106422A...
Page 308: ...Wiring Diagrams SiUS371614E 295 Appendix REYQ144 168TATJU 2D106423A...
Page 318: ...Wiring Diagrams SiUS371614E 305 Appendix VAM1200GVJU 3D073270C...
Page 320: ...Wiring Diagrams SiUS371614E 307 Appendix 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B...
Page 321: ...SiUS371614E Wiring Diagrams Appendix 308 BS6 8Q54TVJ 2D089122B...
Page 322: ...Wiring Diagrams SiUS371614E 309 Appendix BS10 12Q54TVJ 2D089121B...
Page 323: ...Revision History Month Year Version Revised contents 02 2017 SiUS371614E First edition...