Outline of Control (Indoor Unit)
SiUS371614E
93
Functions and Control
9.3
Remote Controller Thermistor
Temperature is controlled by both the remote controller thermistor and suction air thermistor for the
indoor unit. (This is however limited to when the field setting for the remote controller thermistor is
set to Use.)
Note:
When outdoor air is introduced to the air-conditioner with mixed into indoor air, the room
temperature may fail to be set temperature, since TS and TH1 do not enter the area of “use range
of remote control thermistor.” In such a case, put the remote sensor (optional accessory) in your
room, and use it with setting “do not use remote control thermostat.”
∗
FXTQ-TA models do not have this control because they do not have suction air thermistor. The
thermistor is selectable manually when remote sensor (optional accessory) is installed.
Cooling
If there is a significant difference in the set temperature and the suction temperature, fine
adjustment control is carried out using a suction air thermistor, or using the remote controller
thermistor near the position of the user when the suction temperature is near the set temperature.
Assuming the set temperature in the figure above is 24°C (75°F), and the suction
temperature has changed from 18°C (64°F) to 30°C (86°F) (A
→
F):
(This example also assumes there are several other air conditioners, and the suction temperature
changes even when the thermostat is off.)
Suction air thermistor is used for temperatures from 18°C (64°F) to 23°C (73°F) (A
→
C).
Remote controller thermistor is used for temperatures from 23°C (73°F) to 27°C (81°F) (C
→
E).
Suction air thermistor is used for temperatures from 27°C (81°F) to 30°C (86°F) (E
→
F).
Assuming suction temperature has changed from 30
°
C (86°F) to 18
°
C (64°F) (F
→
A):
Suction air thermistor is used for temperatures from 30°C (86°F) to 25°C (77°F) (F
→
D).
Remote controller thermistor is used for temperatures from 25°C (77°F) to 21°C (70°F) (D
→
B).
Suction air thermistor is used for temperatures from 21°C (70°F) to 18°C (64°F) (B
→
A).
Set temperature
(Ts)
32
30
28
26
24
22
20
18
16
˚C
˚C
TH1 = Ts – 1
TH1 = Ts + 1
TH1 = Ts + 3
TH1 = Ts – 3
A
B
C
D
E
F
12
14 16 18 20 22 24 26 28 30 32 34
Range in which remote controller
thermistor can be used
Range in which
suction air thermistor
can be used
Suction temperature (TH1)
Differential
Summary of Contents for REYQ-TA Series
Page 1: ...Service Manual SiUS371614E REYQ72 456TAYDU REYQ72 456TATJU Heat Recovery 60 Hz...
Page 304: ...Wiring Diagrams SiUS371614E 291 Appendix REYQ96 120TAYDU 2D106425A...
Page 305: ...SiUS371614E Wiring Diagrams Appendix 292 REYQ144 168TAYDU 2D106426A...
Page 306: ...Wiring Diagrams SiUS371614E 293 Appendix REYQ72TATJU 3D106421A...
Page 307: ...SiUS371614E Wiring Diagrams Appendix 294 REYQ96 120TATJU 2D106422A...
Page 308: ...Wiring Diagrams SiUS371614E 295 Appendix REYQ144 168TATJU 2D106423A...
Page 318: ...Wiring Diagrams SiUS371614E 305 Appendix VAM1200GVJU 3D073270C...
Page 320: ...Wiring Diagrams SiUS371614E 307 Appendix 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B...
Page 321: ...SiUS371614E Wiring Diagrams Appendix 308 BS6 8Q54TVJ 2D089122B...
Page 322: ...Wiring Diagrams SiUS371614E 309 Appendix BS10 12Q54TVJ 2D089121B...
Page 323: ...Revision History Month Year Version Revised contents 02 2017 SiUS371614E First edition...