Field Setting from Remote Controller
Field Settings
126
Setting the Rate of Human Detection
(For units with the infrared presence/floor sensor only)
Set the sensitivity of the infrared presence sensor.
• The infrared presence sensor can be disabled by selecting the Second code No.
04
.
(Note) When the infrared presence sensor is disabled, the remote controller menu does not display some
functions such as the automatic draft reduction, energy-saving operation in absence and halt in absence.
Airflow Adjustment (AUTO)
External Static Pressure Settings
Make settings in either method (a) or method (b) as explained below.
(a) Use the airflow auto adjustment function to make settings.
Airflow auto adjustment: The volume of discharge air is automatically adjusted to the rated quantity.
(b) Select External Static Pressure with Remote Controller Check that 01 (OFF) is set for the “SECOND CODE No.”
in “MODE No. 21” for airflow adjustment on an indoor unit basis in Table 4. The “SECOND CODE No.” is set to
01 (OFF) at factory setting. Change the “SECOND CODE No.” as shown in table according to the external static
pressure of the duct to be connected.
Compensating the Temperature around People
(For units with the infrared presence/floor sensor only)
Change the ratio between the suction air temperature and floor temperature used to calculate the temperature
around human.
The temperature around human is calculated using the values of the suction air thermistor and the infrared floor
sensor. The factory setting is Normal (the average value of the suction air temperature and the floor temperature
is applied). However, the rate at which the suction air thermistor and the infrared floor sensor affect the
temperature around human can be changed with this setting.
• To reflect the effect of the temperature around the ceiling, select the "Priorities given on the suction air
temperature" (the Second code No.
02
).
• To reflect the effect of the temperature around the floor, select the "Priorities given on the floor temperature"
(the Second code No.
04
).
• The infrared floor sensor can be disabled by selecting "Suction air temperature only" (the Second code No.
01
).
Mode No.
First Code No.
Second Code No.
Contents
11(21)
6
01
High sensitivity
02
Low sensitivity
03
Standard sensitivity
04
Infrared presence sensor disabled
Mode No.
First Code No.
Second Code No.
Contents
11 (21)
7
01
OFF
02
Completion of airflow adjustment
03
Start of airflow adjustment
Mode No.
First Code No.
Second Code No.
Contents
11 (21)
8
01
Suction air temperature only
02
Priorities given on the suction air temperature
03
Standard
04
Priorities given on the floor temperature
Summary of Contents for REYQ-TA Series
Page 1: ...Service Manual SiUS371614E REYQ72 456TAYDU REYQ72 456TATJU Heat Recovery 60 Hz...
Page 304: ...Wiring Diagrams SiUS371614E 291 Appendix REYQ96 120TAYDU 2D106425A...
Page 305: ...SiUS371614E Wiring Diagrams Appendix 292 REYQ144 168TAYDU 2D106426A...
Page 306: ...Wiring Diagrams SiUS371614E 293 Appendix REYQ72TATJU 3D106421A...
Page 307: ...SiUS371614E Wiring Diagrams Appendix 294 REYQ96 120TATJU 2D106422A...
Page 308: ...Wiring Diagrams SiUS371614E 295 Appendix REYQ144 168TATJU 2D106423A...
Page 318: ...Wiring Diagrams SiUS371614E 305 Appendix VAM1200GVJU 3D073270C...
Page 320: ...Wiring Diagrams SiUS371614E 307 Appendix 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B...
Page 321: ...SiUS371614E Wiring Diagrams Appendix 308 BS6 8Q54TVJ 2D089122B...
Page 322: ...Wiring Diagrams SiUS371614E 309 Appendix BS10 12Q54TVJ 2D089121B...
Page 323: ...Revision History Month Year Version Revised contents 02 2017 SiUS371614E First edition...