Refrigerant Circuit
SiUS371614E
19
Refrigerant Circuit
1.4
Branch Selector Unit
1.4.1 Single Branch Selector Unit
BSQ36-96TVJ
Note:
Factory setting of all EV opening: 60 pulse
No.
Name
Electric
symbol
Function
1
Electronic expansion valve (EVH)
Y2E
Opens while in heating operation or all indoor units are in cooling.
(Max : 760 pulse)
2
Electronic expansion valve (EVL)
Y3E
Opens while in cooling. (Max : 760 pulse)
3
Electronic expansion valve (EVSC)
Y1E
In simultaneous cooling and heating operation, it is used to subcooling
liquid refrigerants when an indoor unit downstream of this Branch Selector
unit is in heating. (Max : 480 pulse)
Filter
Filter
Filter
Filter
Liquid pipe
connection port
Gas pipe
connection port
Double pipe heat
exchanger
Electronic
Expansion Valve
(EVSC)
HP/LP gas pipe
connection port
Suction gas pipe
connection port
Electronic
Expansion Valve
(EVH)
Electronic
Expansion Valve
(EVL)
Liquid pipe
connection port
(3)
(1)
(2)
4D085545A
Summary of Contents for REYQ-TA Series
Page 1: ...Service Manual SiUS371614E REYQ72 456TAYDU REYQ72 456TATJU Heat Recovery 60 Hz...
Page 304: ...Wiring Diagrams SiUS371614E 291 Appendix REYQ96 120TAYDU 2D106425A...
Page 305: ...SiUS371614E Wiring Diagrams Appendix 292 REYQ144 168TAYDU 2D106426A...
Page 306: ...Wiring Diagrams SiUS371614E 293 Appendix REYQ72TATJU 3D106421A...
Page 307: ...SiUS371614E Wiring Diagrams Appendix 294 REYQ96 120TATJU 2D106422A...
Page 308: ...Wiring Diagrams SiUS371614E 295 Appendix REYQ144 168TATJU 2D106423A...
Page 318: ...Wiring Diagrams SiUS371614E 305 Appendix VAM1200GVJU 3D073270C...
Page 320: ...Wiring Diagrams SiUS371614E 307 Appendix 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B...
Page 321: ...SiUS371614E Wiring Diagrams Appendix 308 BS6 8Q54TVJ 2D089122B...
Page 322: ...Wiring Diagrams SiUS371614E 309 Appendix BS10 12Q54TVJ 2D089121B...
Page 323: ...Revision History Month Year Version Revised contents 02 2017 SiUS371614E First edition...