Field Setting from Remote Controller
SiUS371614E
131
Field Settings
Optional Kit Setting (UV lamp + Humi Economizer) (for FXTQ-TA model)
Residential Dry (for FXTQ-TA model)
Drain Pump Operation Settings (for FXMQ-PB model)
The drain pump operation can be disabled for natural drainage by changing the following field setting.
Humidification when Heating Thermostat is OFF
Setting to "Humidification Setting" turns ON the humidifier if suction air temperature is 20°C (68°F) or above and
turns OFF the humidifier if suction air temperature is 18°C (64.4°F) or below when the heating thermostat is OFF.
Setting of Direct Duct Connection
This is used when "fresh air intake kit equipped with fan" is connected. The indoor fan carries out residual
operation for one minute after the thermostat is stopped. (For the purpose of preventing dust on the air filter from
falling off.)
Mode No.
First Code No.
Second Code No.
Contents
UV lamp + humidifier fan
speed
Economizer setting for
Mech standby duration
(minutes)
14 (24)
4
01
Refer to controller
10
02
High
10
03
Refer to controller
20
04
High
20
05
Refer to controller
30
06
High
30
07
Refer to controller
40
08
High
40
09
Refer to controller
50
10
High
50
11
Refer to controller
60
12
High
60
13
Refer to controller
Free cooling only
14
High
Free cooling only
Mode No.
First Code No.
Second Code No.
Contents
14 (24)
5
01
Set temperature: room temperature
02
Set temperature: same as cooling set temperature
Mode No.
First Code No.
Second Code No.
Contents
15 (25)
0
01
—
02
ON
03
OFF
Mode No.
First Code No.
Second Code No.
Contents
15 (25)
1
01
Not equipped
02
Setting of humidifier
Mode No.
First Code No.
Second Code No.
Contents
15 (25)
2
01
Without direct duct connection
02
With direct duct connection equipped with fan
Summary of Contents for REYQ-TA Series
Page 1: ...Service Manual SiUS371614E REYQ72 456TAYDU REYQ72 456TATJU Heat Recovery 60 Hz...
Page 304: ...Wiring Diagrams SiUS371614E 291 Appendix REYQ96 120TAYDU 2D106425A...
Page 305: ...SiUS371614E Wiring Diagrams Appendix 292 REYQ144 168TAYDU 2D106426A...
Page 306: ...Wiring Diagrams SiUS371614E 293 Appendix REYQ72TATJU 3D106421A...
Page 307: ...SiUS371614E Wiring Diagrams Appendix 294 REYQ96 120TATJU 2D106422A...
Page 308: ...Wiring Diagrams SiUS371614E 295 Appendix REYQ144 168TATJU 2D106423A...
Page 318: ...Wiring Diagrams SiUS371614E 305 Appendix VAM1200GVJU 3D073270C...
Page 320: ...Wiring Diagrams SiUS371614E 307 Appendix 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B...
Page 321: ...SiUS371614E Wiring Diagrams Appendix 308 BS6 8Q54TVJ 2D089122B...
Page 322: ...Wiring Diagrams SiUS371614E 309 Appendix BS10 12Q54TVJ 2D089121B...
Page 323: ...Revision History Month Year Version Revised contents 02 2017 SiUS371614E First edition...