74
Heating
Pc
<
3.17 MPa
(460 psi)
Pc
<
3.22 MPa
(467 psi)
Pc
>
3.39 MPa
(492 psi)
Pc
>
3.31 MPa
(480 psi)
Pc
>
3.72 MPa
(540 psi)
Normal Operation
9-step down
All units
Compressor step: 1
3-step up
Current step
maintained
High pressure standby
(2 times within 40 minutes)
Pc: High pressure sensor
detection value for master
unit
Abnormal stop
(
E3
is displayed)
Pc
>
3.31 MPa
(480 psi)
After 10
seconds
After 15
seconds
High pressure switch (4.0 MPa
(580 psi)
) is activated