Field Setting from Outdoor Unit
Field Settings
138
Accessing modes
BS1 is used to change the mode you want to access.
• Access mode 1
Press BS1 once. Segment indication changes to:
• Access mode 2
Press BS1 for at least 5 seconds. Segment indication changes to:
Mode 1
Mode 1 is used to set basic settings and to monitor the status of the unit.
•
Changing and access the setting in mode 1:
Once mode 1 is selected (press BS1 once), you can select the wanted setting. It is done by pushing BS2.
Accessing the selected setting's value is done by pressing BS3 once.
•
To quit and return to the initial status, press BS1.
Example:
Checking the content of parameter [1-10] (to know how many indoor units are connected to the system).
Mode: 1
Setting: 10
•
Make sure the segment indication is as during normal operation (default situation when shipped from factory).
•
Press BS1 once; result segment display:
•
Press BS2 10 times; result segment display:
•
Press BS3 1 time; the value which is returned (depending on the actual field situation), is the amount of
indoor units which are connected to the system.
Result: mode1 setting 10 is addressed and selected, return value is monitored information
•
To leave the monitoring function, press BS1 once, you will return to the default situation when shipped from
factory.
Mode 2
Mode 2 is used to set field settings of the outdoor unit and system.
•
Changing and access the setting in mode 2:
Once mode 2 is selected (press BS1 for more than 5 seconds), you can select the wanted setting. It is done
by pressing BS2.
Accessing the selected setting's value is done by pressing BS3 once.
•
To quit and return to the initial status, press BS1.
•
Changing the value of the selected setting in mode 2:
- Once mode 2 is selected (press BS1 for more than 5 seconds) you can select the wanted setting. It is done
by pressing BS2.
- Accessing the selected setting's value is done by pressing BS3 once.
- Now BS2 is used to select the required value of the selected setting.
- When the required value is selected, you can define the change of value by pressing BS3 once.
- Press BS3 again to start operation according to the chosen value.
INFORMATION If you get confused in the middle of the process, press BS1.
Then it returns to idle situation (no indication on segment displays: blank)
Result: mode 1 is accessed.
Result: mode 1 setting 10 is addressed.
Summary of Contents for REYQ-TA Series
Page 1: ...Service Manual SiUS371614E REYQ72 456TAYDU REYQ72 456TATJU Heat Recovery 60 Hz...
Page 304: ...Wiring Diagrams SiUS371614E 291 Appendix REYQ96 120TAYDU 2D106425A...
Page 305: ...SiUS371614E Wiring Diagrams Appendix 292 REYQ144 168TAYDU 2D106426A...
Page 306: ...Wiring Diagrams SiUS371614E 293 Appendix REYQ72TATJU 3D106421A...
Page 307: ...SiUS371614E Wiring Diagrams Appendix 294 REYQ96 120TATJU 2D106422A...
Page 308: ...Wiring Diagrams SiUS371614E 295 Appendix REYQ144 168TATJU 2D106423A...
Page 318: ...Wiring Diagrams SiUS371614E 305 Appendix VAM1200GVJU 3D073270C...
Page 320: ...Wiring Diagrams SiUS371614E 307 Appendix 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B...
Page 321: ...SiUS371614E Wiring Diagrams Appendix 308 BS6 8Q54TVJ 2D089122B...
Page 322: ...Wiring Diagrams SiUS371614E 309 Appendix BS10 12Q54TVJ 2D089121B...
Page 323: ...Revision History Month Year Version Revised contents 02 2017 SiUS371614E First edition...