Check
SiUS371614E
277
Service Diagnosis
4.3
Superheat Operation Check
Identify the defective points referring to the failure factor analysis (FTA) as follows.
Note:
∗
1. Refer to “Low pressure protection control” for hot gas bypass control.
∗
2. Refer to “Subcooling electronic expansion valve control”.
∗
3. “Superheating temperature control” in cooling is conducted by indoor unit electronic expansion valve.
∗
4. Superheating temperature control in heating is conducted by outdoor unit electronic expansion
valve (main).
∗
5. Judgement criteria of superheat operation:
(1) Suction gas superheated degree: 10°C (50°F) and over. (2) Discharge gas superheated degree: 45°C
(113°F) and over, except immediately after compressor starts up or is running under drooping control.
(Use the above values as a guide. Depending on the other conditions, the unit may be normal
despite the values within the above range.)
CHECK 3
Abnormal piping length
Bent or crashed pipe
(Including moisture choke)
Stop valve closed.
Defective valve coil
Defective valve body
Defective valve coil
Defective valve body
←
Are the coil resistance and insulation normal?
←
Are the electric characteristics normal?
←
Are the coil resistance and insulation normal?
←
Is the connector properly connected?
Are the thermistor resistance characteristics normal?
←
Is the connector properly connected?
Are the thermistor resistance characteristics normal?
←
Are the coil resistance and insulation normal?
←
Are the electric characteristics normal?
←
Refer to
CHECK 7
←
Does the piping length fall in the permissible range?
←
Conduct visual checks.
←
Eliminate moisture by vacuum operation. (Refer to
CHECK 8
)
←
Check if the stop valve is open.
Defective
discharge
pipe
temperature
control
Defective hot
gas bypass
control
Hot gas circuit clogging
Defective solenoid
valve coil
Defective solenoid
valve body
Defective service
monitor PCB
Defective service
monitor PCB
Defective valve coil
Defective low
pressure sensor
Defective subcooling
heat exchanger outlet
thermistor
Defective valve
body
Defective
subcooling
electronic
expansion
valve control
Superheat due to
shaft damage
Superheat due to
defective compressor
Defective indoor
unit electronic
expansion valve
Defective
control
Defective
control
Defective
outdoor unit
electronic
expansion valve
Defective four
way valve
operation
[In cooling only]
(
∗
1)
(
∗
2)
Compressor
overheat
Refrigerant
shortage
High pipe
resistance
Defective
superheated
degree
control.
[In cooling]
If the indoor unit
electronic
expansion valve is
throttled too much:
(
∗
3)
[In heating]
If the outdoor unit
electronic
expansion valve
excessively
throttled: (
∗
4)
Temperature
increase of
discharge
pipe
Defective
subcooling
electronic
expansion
valve
←
Are the coil resistance and
insulation normal?
←
Is the connector properly connected?
Are the thermistor resistance characteristics
normal?
←
Is the pressure value checked with the
Service Checker corresponding to the
measurement value of the pressure sensor?
←
Check if the piping temperature connected
to the four way valve is normal.
Four way valve is in the
middle position.
Leak from hot gas bypass
valve
Defective
control
Defective gas pipe
thermistor of indoor unit
Defective thermistor for
indoor unit liquid pipe
Defective service
monitor PCB
Defective low pressure
sensor
Defective suction pipe
thermistor
Defective service
monitor PCB
←
Is the pressure value checked with the Service
Checker corresponding to the measurement
value of the pressure sensor?
←
Is the connector properly connected?
Are the thermistor resistance characteristics normal?
Summary of Contents for REYQ-TA Series
Page 1: ...Service Manual SiUS371614E REYQ72 456TAYDU REYQ72 456TATJU Heat Recovery 60 Hz...
Page 304: ...Wiring Diagrams SiUS371614E 291 Appendix REYQ96 120TAYDU 2D106425A...
Page 305: ...SiUS371614E Wiring Diagrams Appendix 292 REYQ144 168TAYDU 2D106426A...
Page 306: ...Wiring Diagrams SiUS371614E 293 Appendix REYQ72TATJU 3D106421A...
Page 307: ...SiUS371614E Wiring Diagrams Appendix 294 REYQ96 120TATJU 2D106422A...
Page 308: ...Wiring Diagrams SiUS371614E 295 Appendix REYQ144 168TATJU 2D106423A...
Page 318: ...Wiring Diagrams SiUS371614E 305 Appendix VAM1200GVJU 3D073270C...
Page 320: ...Wiring Diagrams SiUS371614E 307 Appendix 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B...
Page 321: ...SiUS371614E Wiring Diagrams Appendix 308 BS6 8Q54TVJ 2D089122B...
Page 322: ...Wiring Diagrams SiUS371614E 309 Appendix BS10 12Q54TVJ 2D089121B...
Page 323: ...Revision History Month Year Version Revised contents 02 2017 SiUS371614E First edition...