Outline of Control (Indoor Unit)
SiUS371614E
111
Functions and Control
9.14 Fan Control (Heater Residual) (FXTQ-TA Models)
Outline
If the indoor heater turned OFF from ON during heating operation, the fan will keep operating for
further period of time in order to cool the heater.
Detail
∗
1. When the heater is ON, the airflow rate of the fan will be whichever is the largest between the
CFM dictated by the heater's own capacity, or the fan tap CFM determined by other controls.
∗
2. Fan residual operation will continue, even if the indoor unit is turned off with the remote
controller operation button.
9.15 Interlocked with External Equipment (FXTQ-TA Models)
9.15.1 Air Purifier (UV lamp)
When an air purifier is connected onsite, the fan is operated with the airflow rate set of the remote
controller or with the H tap.
∗
1. External input ON is an input signal to the X1M-AIR CLEANER terminal on the PCB.
∗
2. Field setting 14(24)-4. Refer to page 131.
9.15.2 Humidifier
When a humidifier is connected onsite, the fan operates with the airflow rate set of the remote
controller or with the H tap.
∗
1. External input ON is an input signal to the X1M-HUMIDIFIER terminal on the PCB.
∗
2. Field setting 14(24)-4. Refer to page 131.
Note:
This control is not applicable to the humidifier connected to the wiring adaptor, but to the humidifier
connected to HUMIDIFIER on the X1M terminal of the indoor unit PCB.
•
Heater turned OFF from ON
OR
•
Heater ON
•
Time up (
∗
2)
Residual OFF
Residual ON
Fan (
∗
1)
ENTRY/
90 sec. timer starts.
&
Fan X tap operation
(X tap is selectable by field setting. (
∗
2))
•
Remote control operation
(including thermostat OFF)
•
External input: ON (
∗
1)
&
&
•
Remote control operation: ON
(including thermostat OFF)
•
When the external input
changes from ON to OFF.
•
Remote control operation: ON
(including thermostat OFF)
•
External input: ON (
∗
1)
Fan X tap operation
(X tap is selectable by field setting. (
∗
2))
Fan residual operation for 30 seconds
(The fan airflow rate is set with the X tap.)
Summary of Contents for REYQ-TA Series
Page 1: ...Service Manual SiUS371614E REYQ72 456TAYDU REYQ72 456TATJU Heat Recovery 60 Hz...
Page 304: ...Wiring Diagrams SiUS371614E 291 Appendix REYQ96 120TAYDU 2D106425A...
Page 305: ...SiUS371614E Wiring Diagrams Appendix 292 REYQ144 168TAYDU 2D106426A...
Page 306: ...Wiring Diagrams SiUS371614E 293 Appendix REYQ72TATJU 3D106421A...
Page 307: ...SiUS371614E Wiring Diagrams Appendix 294 REYQ96 120TATJU 2D106422A...
Page 308: ...Wiring Diagrams SiUS371614E 295 Appendix REYQ144 168TATJU 2D106423A...
Page 318: ...Wiring Diagrams SiUS371614E 305 Appendix VAM1200GVJU 3D073270C...
Page 320: ...Wiring Diagrams SiUS371614E 307 Appendix 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B...
Page 321: ...SiUS371614E Wiring Diagrams Appendix 308 BS6 8Q54TVJ 2D089122B...
Page 322: ...Wiring Diagrams SiUS371614E 309 Appendix BS10 12Q54TVJ 2D089121B...
Page 323: ...Revision History Month Year Version Revised contents 02 2017 SiUS371614E First edition...