Troubleshooting by Error Code
SiUS371614E
225
Service Diagnosis
3.38 Thermistor Abnormality
Error Code
H9, J3, J5, J6, J7, J8, J9
Applicable
Models
All outdoor unit models
Method of Error
Detection
Detect according to temperature detected with individual thermistors.
Error Decision
Conditions
The system is in operation and the thermistor causes wiring disconnection or short circuit in it.
Supposed
Causes
Defective connection of thermistor
Defective thermistor
Defective outdoor unit PCB
Troubleshooting
Thermistor is
connected to the
connector.
Replace the outdoor unit PCB.
Connect the connector and turn
ON again.
NO
NO
Replace the thermistor (
∗
1).
YES
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Resistance
is normal when
measured after
disconnecting the
thermistor from the
outdoor unit PCB.
CHECK 11
(1.8 k
Ω
to
800 k
Ω
)
Summary of Contents for REYQ-TA Series
Page 1: ...Service Manual SiUS371614E REYQ72 456TAYDU REYQ72 456TATJU Heat Recovery 60 Hz...
Page 304: ...Wiring Diagrams SiUS371614E 291 Appendix REYQ96 120TAYDU 2D106425A...
Page 305: ...SiUS371614E Wiring Diagrams Appendix 292 REYQ144 168TAYDU 2D106426A...
Page 306: ...Wiring Diagrams SiUS371614E 293 Appendix REYQ72TATJU 3D106421A...
Page 307: ...SiUS371614E Wiring Diagrams Appendix 294 REYQ96 120TATJU 2D106422A...
Page 308: ...Wiring Diagrams SiUS371614E 295 Appendix REYQ144 168TATJU 2D106423A...
Page 318: ...Wiring Diagrams SiUS371614E 305 Appendix VAM1200GVJU 3D073270C...
Page 320: ...Wiring Diagrams SiUS371614E 307 Appendix 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B...
Page 321: ...SiUS371614E Wiring Diagrams Appendix 308 BS6 8Q54TVJ 2D089122B...
Page 322: ...Wiring Diagrams SiUS371614E 309 Appendix BS10 12Q54TVJ 2D089121B...
Page 323: ...Revision History Month Year Version Revised contents 02 2017 SiUS371614E First edition...