Special Control
SiUS371614E
87
Functions and Control
[While in all-room heating operation or cooling/heating simultaneous operation
→
All-room cooling]
(1) In heating operation or cooling and heating
simultaneous operation
· Using the dual pressure gas pipe as a suction
gas pipe.
(2) Pump-down residual operation
(3) Pre-startup control
· Switching between the electronic expansion
valves of branch selector unit.
· Required switching time: 2 to 4 minutes
(switching control time)
(While switching: The compressor stops
operating.)
(4) Startup control
· Switching the dual pressure gas pipe from low
pressure to high pressure.
(5) Into all-unit cooling operation
· In cool air supply operation
Suction gas pipe
Dual pressure gas pipe
Heating
Heating
Heating
Heating
Heating
Suction gas pipe
Dual pressure gas pipe
Vent
Vent
Vent
Vent
Vent
Cooling
Cooling
Cooling
Cooling
Suction gas pipe
Dual pressure gas pipe
Cooling
���
���
���
���
���
���
���
���
���
���
���
���
���
���
���
Liquid
pipe
Liquid
pipe
Liquid
pipe
Summary of Contents for REYQ-TA Series
Page 1: ...Service Manual SiUS371614E REYQ72 456TAYDU REYQ72 456TATJU Heat Recovery 60 Hz...
Page 304: ...Wiring Diagrams SiUS371614E 291 Appendix REYQ96 120TAYDU 2D106425A...
Page 305: ...SiUS371614E Wiring Diagrams Appendix 292 REYQ144 168TAYDU 2D106426A...
Page 306: ...Wiring Diagrams SiUS371614E 293 Appendix REYQ72TATJU 3D106421A...
Page 307: ...SiUS371614E Wiring Diagrams Appendix 294 REYQ96 120TATJU 2D106422A...
Page 308: ...Wiring Diagrams SiUS371614E 295 Appendix REYQ144 168TATJU 2D106423A...
Page 318: ...Wiring Diagrams SiUS371614E 305 Appendix VAM1200GVJU 3D073270C...
Page 320: ...Wiring Diagrams SiUS371614E 307 Appendix 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B...
Page 321: ...SiUS371614E Wiring Diagrams Appendix 308 BS6 8Q54TVJ 2D089122B...
Page 322: ...Wiring Diagrams SiUS371614E 309 Appendix BS10 12Q54TVJ 2D089121B...
Page 323: ...Revision History Month Year Version Revised contents 02 2017 SiUS371614E First edition...