SiUS371614E
Troubleshooting by Error Code
Service Diagnosis
178
3.5
Indoor Fan Motor Abnormality
3.5.1 Indoor Fan Motor Abnormality (FXDQ, FXHQ Models)
Error Code
A6
Applicable
Models
FXDQ, FXHQ
Method of Error
Detection
This error is detected if there is no revolutions detection signal output from the fan motor.
Error Decision
Conditions
When no revolutions can be detected even at the maximum output voltage to the fan
Supposed
Causes
Defective indoor fan motor
Broken wires
Defective contact
Troubleshooting
NO
YES
YES
Is
the X4A
connector securely
connected?
NO
Is
the
power of 12
VDC supplied
between the Pins 1
and 3 when the X4A is
disconnected and
the power
supply turns
ON?
Replace the indoor unit main
PCB (A1P).
Properly connect the
connectors.
(At this time, check for any
defective connector contact or
broken wires.)
Check the indoor fan motor and
the wiring circuits of the motor.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for REYQ-TA Series
Page 1: ...Service Manual SiUS371614E REYQ72 456TAYDU REYQ72 456TATJU Heat Recovery 60 Hz...
Page 304: ...Wiring Diagrams SiUS371614E 291 Appendix REYQ96 120TAYDU 2D106425A...
Page 305: ...SiUS371614E Wiring Diagrams Appendix 292 REYQ144 168TAYDU 2D106426A...
Page 306: ...Wiring Diagrams SiUS371614E 293 Appendix REYQ72TATJU 3D106421A...
Page 307: ...SiUS371614E Wiring Diagrams Appendix 294 REYQ96 120TATJU 2D106422A...
Page 308: ...Wiring Diagrams SiUS371614E 295 Appendix REYQ144 168TATJU 2D106423A...
Page 318: ...Wiring Diagrams SiUS371614E 305 Appendix VAM1200GVJU 3D073270C...
Page 320: ...Wiring Diagrams SiUS371614E 307 Appendix 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B...
Page 321: ...SiUS371614E Wiring Diagrams Appendix 308 BS6 8Q54TVJ 2D089122B...
Page 322: ...Wiring Diagrams SiUS371614E 309 Appendix BS10 12Q54TVJ 2D089121B...
Page 323: ...Revision History Month Year Version Revised contents 02 2017 SiUS371614E First edition...