Service Diagnosis
200
3.22 Remote Sensor Abnormality
Error Code
C9
Applicable
Models
FXTQ-TA
Method of Error
Detection
The error is detected by remote sensor temperature.
Error Decision
Conditions
The remote sensor becomes disconnected or shorted while the unit is running.
Supposed
Causes
Defective indoor unit thermistor (R1T) for room temperature
Defective indoor unit PCB
Troubleshooting
Note:
∗
1. Connector and indoor unit PCB
Is the
optional remote
sensor is installed?
Field
setting 10(20)-2 is set to
03.
Connector is
connected to the indoor
unit PCB (
∗
1).
Resistance
is normal when
measured after
disconnecting the sensor
from the indoor unit
PCB.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Set to 03.
Replace the indoor unit PCB.
NO
NO
YES
YES
Replace the indoor unit PCB.
Connect the sensor and turn ON
again.
NO
NO
Replace the sensor (R1T).
YES
YES
CHECK 11
Connector for remote sensor
PCB
X4A
A1P
CHECK 11
Summary of Contents for REYQ-TA Series
Page 1: ...Service Manual SiUS371614E REYQ72 456TAYDU REYQ72 456TATJU Heat Recovery 60 Hz...
Page 304: ...Wiring Diagrams SiUS371614E 291 Appendix REYQ96 120TAYDU 2D106425A...
Page 305: ...SiUS371614E Wiring Diagrams Appendix 292 REYQ144 168TAYDU 2D106426A...
Page 306: ...Wiring Diagrams SiUS371614E 293 Appendix REYQ72TATJU 3D106421A...
Page 307: ...SiUS371614E Wiring Diagrams Appendix 294 REYQ96 120TATJU 2D106422A...
Page 308: ...Wiring Diagrams SiUS371614E 295 Appendix REYQ144 168TATJU 2D106423A...
Page 318: ...Wiring Diagrams SiUS371614E 305 Appendix VAM1200GVJU 3D073270C...
Page 320: ...Wiring Diagrams SiUS371614E 307 Appendix 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B...
Page 321: ...SiUS371614E Wiring Diagrams Appendix 308 BS6 8Q54TVJ 2D089122B...
Page 322: ...Wiring Diagrams SiUS371614E 309 Appendix BS10 12Q54TVJ 2D089121B...
Page 323: ...Revision History Month Year Version Revised contents 02 2017 SiUS371614E First edition...