SiUS371614E
Field Setting from Outdoor Unit
Field Settings
140
2.4
Monitoring Function and Field Settings
The operation of the outdoor unit can further be defined by changing some field settings. Next to making field
settings it is also possible to confirm the current operation parameters of the unit. The setting can also be
performed via the PC configuration software.
Below relevant Monitoring mode (mode 1) and Field setting mode (mode 2) settings are explained in detail.
Making settings is done via the master outdoor unit.
2.4.1 Mode 1
Mode 1 can be used to monitor the current situation of the outdoor unit. Some field setting contents can be
monitored as well.
Below the settings in mode 1 are explained.
[1-0]:
shows whether the unit you check is a master, slave 1 or slave 2 unit
• No indication: undefined situation
• 0: outdoor unit is master unit
• 1: outdoor unit is slave 1 unit
• 2: outdoor unit is slave 2 unit
Master, slave 1 and slave 2 indications are relevant in multiple outdoor unit system configurations. The
allocation of which outdoor unit is master, slave 1 or slave 2 are decided by the unit’s logic.
The master unit should be used to input field settings in mode 2.
[1-1]:
shows the status of night-time low noise operation
• 1: unit is currently operating under low noise restrictions
• 0: unit is currently not operating under low noise restrictions
Night-time low noise operation reduces the sound generated by the unit compared to nominal operating
conditions.
Night-time low noise operation can be set in mode 2. There are two methods to activate night-time low
noise operation of the outdoor unit system.
The first method is to enable an automatic night-time low noise operation during night time by field
setting. The unit will operate at the selected low noise level during the selected time frames.
The second method is to enable night-time low noise operation based on an external input. For this
operation an optional accessory is required.
[1-2]:
shows the status of power consumption limitation operation
• 1: unit is currently operating under power consumption limitation
• 0: unit is currently not operating under power consumption limitations
Power consumption limitation reduces the power consumption of the unit compared to nominal operating
conditions.
Power consumption limitation can be set in mode 2.
There are two methods to activate power consumption limitation of the outdoor unit system.
The first method is to enable a forced power consumption limitation by field setting. The unit will always
operate at the selected power consumption limitation.
The second method is to enable power consumption limitation based on an external input. For this
operation an optional accessory is required.
Summary of Contents for REYQ-TA Series
Page 1: ...Service Manual SiUS371614E REYQ72 456TAYDU REYQ72 456TATJU Heat Recovery 60 Hz...
Page 304: ...Wiring Diagrams SiUS371614E 291 Appendix REYQ96 120TAYDU 2D106425A...
Page 305: ...SiUS371614E Wiring Diagrams Appendix 292 REYQ144 168TAYDU 2D106426A...
Page 306: ...Wiring Diagrams SiUS371614E 293 Appendix REYQ72TATJU 3D106421A...
Page 307: ...SiUS371614E Wiring Diagrams Appendix 294 REYQ96 120TATJU 2D106422A...
Page 308: ...Wiring Diagrams SiUS371614E 295 Appendix REYQ144 168TATJU 2D106423A...
Page 318: ...Wiring Diagrams SiUS371614E 305 Appendix VAM1200GVJU 3D073270C...
Page 320: ...Wiring Diagrams SiUS371614E 307 Appendix 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B...
Page 321: ...SiUS371614E Wiring Diagrams Appendix 308 BS6 8Q54TVJ 2D089122B...
Page 322: ...Wiring Diagrams SiUS371614E 309 Appendix BS10 12Q54TVJ 2D089121B...
Page 323: ...Revision History Month Year Version Revised contents 02 2017 SiUS371614E First edition...