3
|
Components
Service manual
63
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
a
a
A
A
Class 42~71 unit
a
Compressor pipe
a
a
a
Compressor pipe
CAUTION
Overheating the compressor pipes (and the oil inside the compressor pipes) will
damage or destroy the compressor.
6
After soldering is done, stop the nitrogen supply after the component has
cooled‑down.
7
Install the putty on the compressor accumulator.
8
Install the compressor thermal protector, see
70].
9
Connect the Faston connectors to the compressor wire terminals U, V and W