3
|
Components
Service manual
57
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
Prerequisite:
Recuperate the refrigerant from the refrigerant circuit, see
209].
1
If needed, remove any parts to create more space for the removal of the
compressor.
DANGER: RISK OF ELECTROCUTION
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure
the rectifier voltage is below 10 V DC before proceeding.
2
Remove the cover of the compressor wire terminals.
a
A
A
Class 20~35 unit
a
Compressor wire terminals cover
a
A
A
Class 42~71 unit
a
Compressor wire terminals cover