![background image](http://html1.mh-extra.com/html/daikin/perfera-arxm-r-series/perfera-arxm-r-series_service-manual_2460267251.webp)
6
|
Technical data
Service manual
251
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
6.7 Field settings
6.7.1 To control heating only mode
Prerequisite:
Stop operation of the unit.
1
Press
,
, and
simultaneously.
2
Press
.
3
Select SU.
4
Press
to confirm.
5
Press
.
6
Select 19.
7
Press
to confirm.
8
Press
.
9
Select 1 (0: factory setting, 1: heating only).
10
Press
to confirm.
6.7.2 To adjust target set temperature in heating operation
INFORMATION
When there is a big difference between the indoor room temperature and the set
temperature in heating mode, adjust the target set temperature field setting.
▪
Target temperature = remote controller set temperature + 2.5°C. For
example:
Remote controller set temperature = 20°C
Target temperature = 20°C + 2.5°C = 22.5°C
Thermo off temperature = 24.5°C
1
Press
,
, and
simultaneously.
2
Press
.
3
Select SU.
4
Press
to confirm.
5
Press
.
6
Select 7.
7
Press
to confirm.
8
Press
.
9
Select the value to set the desired target temperature:
▪
0 = –2,0°C
▪
1 = –1,0°C
▪
2 = 0°C (factory setting)
▪
3 = +1,0°C
▪
4 = +2,0°C
10
Press
to confirm.