3.17 Swing flap motor
3.17.1 Wall mounted indoor units - Class 20~42
Checking procedures
To perform an electrical check of the swing flap motor
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
151].
1
Disconnect the swing flap motor connector from the indoor unit main PCB.
2
Measure the resistance between the following pins of the motor connector.
Result:
The measurements MUST be as shown in the table below.
Pins
Measured resistance (Ω)
5-1
232.5~267.5
5-2
5-3
5-4
1-2
465~535
1-3
1-4
2-3
2-4
3-4
Swing flap motor resistance
measurements are correct?
Action
Yes
Return to the troubleshooting of the
specific error and continue with the
next procedure.
No
Replace the swing flap motor, see
172].
Repair procedures
To remove the swing flap motor
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
151].
1
Remove the switch box, see
2
As the swing flap motor wiring harness is also connected to the swing raster
motor, remove the swing raster motor, see
3
Remove the swing flap from the indoor unit (by clicking it out).
4
Remove the screw that fixes the swing flap motor.