3
|
Components
Service manual
169
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
Is the resistance measurement correct? Action
No
169].
4
Measure the inductance of the reactor using an LCR meter.
Result:
The inductance MUST be as follows:
Measuring points
Resistance
c‑d
88.5~101.5 µH
d
d
c
c
a
b
c
d
c
d
a
L803
b
L804
c
Measuring point
d
Measuring point
Is the inductance measurement
correct?
Action
Yes
Return to the troubleshooting of the
specific error and continue with the
next step.
No
169].
3.15.2 Repair procedures
As the reactors are part of the main PCB, replace the complete main PCB. See
3.16 Streamer unit
3.16.1 Checking procedures
1
As there is no specific check procedure for this component, first perform a
check of the indoor unit main PCB to check if the streamer unit needs to be
replaced. See
After complete check of the indoor unit
main PCB, is the problem solved?
Action
Yes
No further actions required.