Control Specification
Si04-306
50
Function and Control
3. Determine lower limit frequency
Set a maximum value as an lower limit frequency among the frequency lower limits of the
following functions:
Pressure difference upkeep.
4. Determine prohibited frequency
There is a certain prohibited frequency such as a power supply frequency.
Indoor Frequency Command (
∆
D signal)
The difference between a room temperature and the temperature set by the remote controller
will be taken as the “
∆
D signal” and is used for frequency command.
∗
Th OFF = Thermostat OFF
Frequency Initial Setting
Outline
When starting the compressor, or when conditions are varied due to the change of the room, the
frequency must be initialized according to the total of a maximum
∆
D value of the indoor unit
and the Q value of the indoor unit.
Q value: Indoor unit output determined from indoor unit volume, air flow rate and other factors.
PI Control
(Determine Frequency Up/Down by
∆
D Signal)
1. P control
Calculate
∆
D value in each sampling time (20 seconds), and adjust the frequency according
to its difference from the frequency previously calculated.
2. I control
If the operating frequency is not change more than a certain fixed time, adjust the frequency
up and down according to the
∆
D value, obtaining the fixed
∆
D value.
When the
∆
D value is small...lower the frequency.
When the
∆
D value is large...increase the frequency.
3. Limit of frequency variation width
When the difference between input current and input current drooping value is less than 1.5
A, the frequency increase width must be limited.
4. Frequency management when other controls are functioning
When frequency is drooping;
Frequency management is carried out only when the frequency droops.
For limiting lower limit
Frequency management is carried out only when the frequency rises.
5. Upper and lower limit of frequency by PI control
The frequency upper and lower limits are set depending on indoor unit.
When low noise commands come from the indoor unit or when outdoor unit low noise or
quiet commands come from indoor unit, the upper limit frequency must be lowered than the
usual setting.
Temperature
difference
∆
D
signal
Temperature
difference
∆
D
signal
Temperature
difference
∆
D
signal
Temperature
difference
∆
D
signal
0
∗
Th
OFF
2.0
4
4.0
8
6.0
C
0.5
1
2.5
5
4.5
9
6.5
D
1.0
2
3.0
6
5.0
A
7.0
E
1.5
3
3.5
7
5.5
B
7.5
F
Summary of Contents for FTKD50BVM
Page 17: ...List of Functions Si04 306 8 List of Functions ...
Page 35: ...Specifications Si04 306 26 Specifications ...
Page 143: ...Check Si04 306 134 Service Diagnosis ...
Page 187: ...Outdoor Unit Si04 306 178 Removal Procedure ...
Page 191: ...Others Si04 306 182 Others ...
Page 201: ...Wiring Diagrams Si04 306 192 Appendix FTKD 18 24 28 BVMS ...
Page 203: ...Wiring Diagrams Si04 306 194 Appendix RKD 18 24 28 BVMS ...