Main Functions
Si04-306
38
Function and Control
1.4
Programme Dry Function
Programme dry function removes humidity while preventing the room temperature from
lowering.
Since the microcomputer controls both the temperature and air flow volume, the temperature
adjustment and fan adjustment buttons are inoperable in this mode.
In Case of
Inverter Units
The microcomputer automatically sets the temperature and fan settings. The difference
between the room temperature at startup and the temperature set by the microcomputer is
divided into two zones. Then, the unit operates in the dry mode with an appropriate capacity for
each zone to maintain the temperature and humidity at a comfortable level.
Room temperature at
startup
Temperature (ON point)
at which operation starts
Frequency switching
point
Temperature difference
for operation stop
24ºC
Room temperature at
startup
0.5ºC
1.5ºC
18ºC
18ºC
1.0ºC
17ºC
—
0.5˚C
LHz
LHz
LHz
*
55Hz
*
55Hz
LHz indicates low frequency. Item marked with varies depending on models.
ON point
OFF point
5 min
5 min
Compressor
control
Stop
Stop
Stop
Stop
Stop
Stop
Indoor unit fan
Extra-low air flow
Extra-low air flow
Low air flow
Low air flow
(R1359)
Frequency
switching
point
Summary of Contents for FTKD50BVM
Page 17: ...List of Functions Si04 306 8 List of Functions ...
Page 35: ...Specifications Si04 306 26 Specifications ...
Page 143: ...Check Si04 306 134 Service Diagnosis ...
Page 187: ...Outdoor Unit Si04 306 178 Removal Procedure ...
Page 191: ...Others Si04 306 182 Others ...
Page 201: ...Wiring Diagrams Si04 306 192 Appendix FTKD 18 24 28 BVMS ...
Page 203: ...Wiring Diagrams Si04 306 194 Appendix RKD 18 24 28 BVMS ...