Si04-306
Troubleshooting
Service Diagnosis
107
Troubleshooting
Check No.5
Refer to P.127
Check No.6
Refer to P.128
Check No.11
Refer to P.131
Correct.
Reconnect.
Replace the four way valve
coil.
Replace the outdoor unit
PCB.
Reconnect in position.
Replace a defective
thermistor.
Refer to the refrigerant line
check procedure.
Replace the four way valve
(defective or dust-clogged).
(R2845)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Four way valve coil
disconnected (loose)?
YES
YES
NO
Functioning
NO
Check No. 11
Check the refrigerant line.
Malfunctioning
l
Insufficient gas
l
Water mixed
l
Stop valve defective
Harness out of connector?
NO
YES
Disconnect the
harness from
the connector.
Resistance between
harnesses about
1500 ohms?
Malfunctioning
Functioning
Check No. 5
Check the four way valve
switching output.
YES
NO
Any thermistor disconnected?
Malfunctioning
Functioning
Check No. 6
Check the thermistors.
Check the continuity of the four
way valve coil and harness.
Summary of Contents for FTKD50BVM
Page 17: ...List of Functions Si04 306 8 List of Functions ...
Page 35: ...Specifications Si04 306 26 Specifications ...
Page 143: ...Check Si04 306 134 Service Diagnosis ...
Page 187: ...Outdoor Unit Si04 306 178 Removal Procedure ...
Page 191: ...Others Si04 306 182 Others ...
Page 201: ...Wiring Diagrams Si04 306 192 Appendix FTKD 18 24 28 BVMS ...
Page 203: ...Wiring Diagrams Si04 306 194 Appendix RKD 18 24 28 BVMS ...