
Si04-306
Troubleshooting
Service Diagnosis
111
Troubleshooting
Check No.12
Refer to P.132
Turn off the power and turn it on
again.
Check No. 12
Check the capacitor voltage.
Replace the outdoor unit
PCB.
* Inverter checker
Part No.: 1225477
Correct the power supply or
replace the SPM.
(Replace the outdoor unit
PCB.)
Replace the outdoor unit
PCB.
Replace the compressor.
Replace the outdoor unit
PCB.
Check the supply voltage.
(R2848)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
∗
Running current
as shown at right with relay
cable 1 or 2?
YES
Current
(guideline)
2 sec
Time
Rising with increasing
frequency
Capacitor charged when
the indoor unit or outdoor
unit main relay turns on
NO
NO
DC380±30V?
YES
Voltage within
the allowable range (Supply
voltage±15%)?
YES
NO
Any LED off?
Compressor running?
YES
NO
YES
NO
Get the system started.
Measure the rectifier input voltage.
Turn off the power. Disconnect the
harnesses U, V and W.
Check with the inverter checker (
∗
).
Turn off the power and reconnect
the above harnesses. Then turn on
the power again and get the
system restarted.
Summary of Contents for FTKD50BVM
Page 17: ...List of Functions Si04 306 8 List of Functions ...
Page 35: ...Specifications Si04 306 26 Specifications ...
Page 143: ...Check Si04 306 134 Service Diagnosis ...
Page 187: ...Outdoor Unit Si04 306 178 Removal Procedure ...
Page 191: ...Others Si04 306 182 Others ...
Page 201: ...Wiring Diagrams Si04 306 192 Appendix FTKD 18 24 28 BVMS ...
Page 203: ...Wiring Diagrams Si04 306 194 Appendix RKD 18 24 28 BVMS ...