Si04-306
Indoor Unit
Removal Procedure
149
1.5
Removal of the Heat Exchanger
Procedure
Warning Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure
Points
Remove the electrical
box.
Caution
If gas leaks, repair the spot of
leaking, then collect all
refrigerant from the unit. After
conducting vacuum drying,
recharge proper amount of
refrigerant.
Caution
Do not contaminate any gas
(including air) other than the
specified refrigerant (R22 or
R410A, depending on the
model) into refrigerant cycle.
(Contaminating of air or other
gas causes abnormal high
pressure in refrigerating
cycle, and this results in pipe
breakage or personal
injuries.)
Pay attention so that the
residual water in the
drain
will not make the floor wet.
In case that a drain hose is
buried inside a wall, remove
it after the drain hose in the
wall is pulled out.
1. Disconnect the refrigerant
piping.
1
Hold the indoor unit up
by a piece of wood etc..
2
Unscrew the flare nut
for
gas piping
by two
wrenches.
Use two wrenches to
disconnected pipes.
When disconnecting pipes,
cover every nozzle with caps
so as not to let dust and
moisture in.
3
Unscrew the flare nut
for
liquid piping
by two
wrenches.
Summary of Contents for FTKD50BVM
Page 17: ...List of Functions Si04 306 8 List of Functions ...
Page 35: ...Specifications Si04 306 26 Specifications ...
Page 143: ...Check Si04 306 134 Service Diagnosis ...
Page 187: ...Outdoor Unit Si04 306 178 Removal Procedure ...
Page 191: ...Others Si04 306 182 Others ...
Page 201: ...Wiring Diagrams Si04 306 192 Appendix FTKD 18 24 28 BVMS ...
Page 203: ...Wiring Diagrams Si04 306 194 Appendix RKD 18 24 28 BVMS ...