Troubleshooting
Si04-306
102
Service Diagnosis
4.8
Compressor Lock
Remote
Controller
Display
E6
Method of
Malfunction
Detection
A compressor lock is detected by checking the compressor running condition through the
position detection circuit.
Malfunction
Decision
Conditions
The position detection circuit detects a compressor frequency of below 10 Hz for 20 seconds
or a frequency of above 160 Hz.
40 seconds after the compressor has started, the position detection circuit detects a
compressor frequency of above 180 Hz.
The system will be shut down if the error occurs 16 times.
Clearing condition: Continuous run for about 5 minutes (normal)
Supposed
Causes
Compressor locked
Troubleshooting
Turn off the power. Disconnect the
harnesses U, V and W.
∗
Inverter checker
Part No.: 1225477
Correct the power supply or
replace the SPM.
(Replace the outdoor unit
PCB.)
Replace the compressor.
Check the electronic
expansion valve.
Replace it as required.
Replace the compressor.
(R2842)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
NO
YES
YES
System shut
down after errors repeated
several times?
NO
NO
Normal?
YES
Emergency stop
without compressor
running?
Check with the inverter checker (
∗
).
Turn off the power and reconnect
the harnesses. Turn on the power
again and get the system restarted.
Summary of Contents for FTKD50BVM
Page 17: ...List of Functions Si04 306 8 List of Functions ...
Page 35: ...Specifications Si04 306 26 Specifications ...
Page 143: ...Check Si04 306 134 Service Diagnosis ...
Page 187: ...Outdoor Unit Si04 306 178 Removal Procedure ...
Page 191: ...Others Si04 306 182 Others ...
Page 201: ...Wiring Diagrams Si04 306 192 Appendix FTKD 18 24 28 BVMS ...
Page 203: ...Wiring Diagrams Si04 306 194 Appendix RKD 18 24 28 BVMS ...