Si04-306
Troubleshooting
Service Diagnosis
103
4.9
DC Fan Lock
Remote
Controller
Display
E7
Method of
Malfunction
Detection
A fan motor or related error is detected by checking the high-voltage fan motor rpm being
detected by the hall IC.
Malfunction
Decision
Conditions
The fan does not start in 30 seconds even when the fan motor is running.
The system will be shut down if the error occurs 16 times.
Clearing condition: Continuous run for about 5 minutes (normal)
Supposed
Causes
Fan motor breakdown
Harness or connector disconnected between fan motor and PCB or in poor contact
Foreign matters stuck in the fan
Troubleshooting
Check No.15
Refer to P.133
Turn off the power and
reconnect the connector.
Remove.
Replace the outdoor unit
fan motor.
Replace the outdoor unit
PCB.
(R2843)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Fan motor connector
disconnected?
YES
YES
NO
YES
NO
Pulse signal inputted?
NO
Foreign matters in or
around the fan?
Get started.
Check No. 15
Check the outdoor unit PCB rpm
pulse input.
Summary of Contents for FTKD50BVM
Page 17: ...List of Functions Si04 306 8 List of Functions ...
Page 35: ...Specifications Si04 306 26 Specifications ...
Page 143: ...Check Si04 306 134 Service Diagnosis ...
Page 187: ...Outdoor Unit Si04 306 178 Removal Procedure ...
Page 191: ...Others Si04 306 182 Others ...
Page 201: ...Wiring Diagrams Si04 306 192 Appendix FTKD 18 24 28 BVMS ...
Page 203: ...Wiring Diagrams Si04 306 194 Appendix RKD 18 24 28 BVMS ...