Outdoor Unit
Si04-306
166
Removal Procedure
9
Disconnect the
connectors.
S31: to the SPM
S32: to the SPM
S33: to the MID
S71: to the MID
S91: fin thermistor
10
Control PCB (outdoor
unit)
S10
: to the terminal
strip
S20
: electronic
expansion valve
S31
: to
CN14
of the
SPM
S32
: to
CN11
of the
SPM
S33
: to
S34
of the MID
S40
: overload protector
S51
: to
S52
of the
service monitor PCB
S71
: to
S72
of the MID
S80
: four way valve
S90
: thermistors
(discharge pipe,
outdoor air,
heat exchanger)
S91
: fin thermistor
S101
: to
S102
of the
service monitor PCB
Step
Procedure
Points