3/7
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
A.3.1.1.1
R/W
0: Fixed
1: Weather dep.
2: Fixed / scheduled
3: WD / scheduled
A.3.1.1.2.1
[9-01]
Temperature range
Minimum temp (heating)
R/W
15~37°C, step: 1°C
25°C
A.3.1.1.2.2
[9-00]
Temperature range
Maximum temp (heating)
R/W
37~60°C, step: 1°C
55°C
A.3.1.1.2.3
[9-03]
Temperature range
Minimum temp (*)
R/W
5~18°C, step: 1°C
5°C
A.3.1.1.2.4
[9-02]
Temperature range
Maximum temp (*)
R/W
18~22°C, step: 1°C
22°C
A.3.1.1.5
[8-05]
R/W
0: No
1: Yes
A.3.1.1.7
[2-0C]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
└──────────────────
Additional
A.3.1.2.1
R/W
0: Fixed
1: Weather dep.
2: Fixed / scheduled
3: WD / scheduled
A.3.1.2.2.1
[9-05]
Temperature range
Minimum temp (heating)
R/W
15~37°C, step: 1°C
25°C
A.3.1.2.2.2
[9-06]
Temperature range
Maximum temp (heating)
R/W
37~60°C, step: 1°C
55°C
A.3.1.2.2.3
[9-07]
Temperature range
Minimum temp (*)
R/W
5~18°C, step: 1°C
5°C
A.3.1.2.2.4
[9-08]
Temperature range
Maximum temp (*)
R/W
18~22°C, step: 1°C
22°C
└──────────────────
Delta T source
A.3.1.3.1
[1-0B]
R/W
3~10°C, step: 1°C
5°C
A.3.1.3.2
[1-0D]
R/W
3~10°C, step: 1°C
5°C
└─
Room thermostat
A.3.2.1.1
[3-07]
Room temp. range
Minimum temp (heating)
R/W
12~18°C, step: A.3.2.4
12°C
A.3.2.1.2
[3-06]
Room temp. range
Maximum temp (heating)
R/W
18~30°C, step: A.3.2.4
30°C
A.3.2.1.3
[3-09]
Room temp. range
Minimum temp (*)
R/W
15~25°C, step: A.3.2.4
15°C
A.3.2.1.4
[3-08]
Room temp. range
Maximum temp (*)
R/W
25~35°C, step: A.3.2.4
35°C
A.3.2.2
[2-0A]
R/W
-5~5°C, step: 0,5°C
0°C
A.3.2.4
R/W
0: 1°C
1: 0,5°C
└─
Operation range
A.3.3.1
[4-02]
R/W
14~35°C, step: 1°C
22°C
A.3.3.2
[F-01]
R/W
10~35°C, step: 1°C
20°C
└─
Domestic hot water (DHW)
└─
Type
A.4.1
[6-0D]
R/W
0: Reheat only
1: sched.
2: Scheduled only
└─
Disinfection
A.4.4.1
[2-01]
R/W
0: No
1: Yes
A.4.4.2
[2-00]
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
A.4.4.3
[2-02]
R/W
0~23 hour, step: 1 hour
1
A.4.4.4
[2-03]
R/W
fixed value
60°C
A.4.4.5
[2-04]
R/W
40~60 min, step: 5 min
40 min
└─
Maximum setpoint
A.4.5
[6-0E]
R/W
40~60°C, step: 1°C
60°C
└─
SP mode
A.4.6
R/W
0: Fixed
1: Weather dep.
└─
Weather dependent curve
A.4.7
[0-0B]
Weather-dependent curve
DHW setpoint for high ambient temp. for DHW
WD curve.
R/W
35~[6-0E]°C, step: 1°C
55°C
A.4.7
[0-0C]
Weather-dependent curve
DHW setpoint for low ambient temp. for DHW
WD curve.
R/W
45~[6-0E]°C, step: 1°C
60°C
A.4.7
[0-0D]
Weather-dependent curve
High ambient temp. for DHW WD curve.
R/W
10~25°C, step: 1°C
15°C
A.4.7
[0-0E]
Weather-dependent curve
Low ambient temp. for DHW WD curve.
R/W
-40~5°C, step: 1°C
-10°C
└─
Heat sources
└─
Backup heater
A.5.1.4
[5-01]
R/W
-15~35°C, step: 1°C
0°C
A.5.1.5
[8-0E]
R/W
-15~-7°C, step: 1°C
-7°C
└─
System operation
└─
Auto restart
A.6.1
[3-00]
R/W
0: No
1: Yes
└─
Pwr consumpt. Control
A.6.3.1
[4-08]
R/W
0: No limitation
1: Continuous
2: Digital inputs
A.6.3.2
[4-09]
R/W
0: Current
1: Power
A.6.3.3
[5-05]
R/W
0~50 A, step: 1 A
50 A
Modulated LWT
Emitter type
Mode
Amp. value
Equilibrium temp.
BUH only ambient temp.
Type
Operation day
Start time
Temperature target
Duration
Room temp. step
Space heating OFF temp
Disinfection
Room temp. offset
Space Cooling ON temp (*)
Delta T cooling (*)
LWT setpoint mode
Delta T heating
LWT setpoint mode
(*) Setting is not applicable for this unit
4P4596829-1 - 2019.10
Summary of Contents for ERLA03DAV3
Page 1: ...Installer reference guide Daikin Altherma 3 R F ERLA03DAV3 EHFZ03S18DJ3V...
Page 182: ...1 7 Field settings table 6 8 2 ID9E51 Applicable units EHFZ03S18DJ3V Notes 4P596829 1 2019 10...
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ...4P596821 1A 2020 05 Copyright 2019 Daikin Verantwortung f r Energie und Umwelt...