9
|
Configuration
Installer reference guide
135
ERLA EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1A – 2020.05
#
Code
Description
N/A
[9‑0E]
Pump speed limitation
main zone
▪
0: No limitation.
▪
1~4: General limitation. There is limitation in all
conditions. The required delta T control and
comfort are
NOT
guaranteed.
▪
5~8 (default: 6): Limitation when no actuators.
When there is no heating output, the pump
speed limitation is applicable. When there is
heating output, the pump speed is only
determined by delta T in relation to the
required capacity. With this limitation range,
delta T is possible and the comfort is
guaranteed.
N/A
[9‑0D]
Pump speed limitation
additional zone
▪
0: No limitation.
▪
1~4: General limitation. There is limitation in all
conditions. The required delta T control and
comfort are
NOT
guaranteed.
▪
5~8 (default: 6): Limitation when no actuators.
When there is no heating output, the pump
speed limitation is applicable. When there is
heating output, the pump speed is only
determined by delta T in relation to the
required capacity. With this limitation range,
delta T is possible and the comfort is
guaranteed.
The maximum values depend on the unit type:
[9-0D]=0
[9-0D]=5
a (kPa)
b (l/min)
a (kPa)
b (l/min)
a (kPa)
b (l/min)
a (kPa)
b (l/min)
[9-0D]=6
[9-0D]=7
Summary of Contents for ERLA03DAV3
Page 1: ...Installer reference guide Daikin Altherma 3 R F ERLA03DAV3 EHFZ03S18DJ3V...
Page 182: ...1 7 Field settings table 6 8 2 ID9E51 Applicable units EHFZ03S18DJ3V Notes 4P596829 1 2019 10...
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ...4P596821 1A 2020 05 Copyright 2019 Daikin Verantwortung f r Energie und Umwelt...