9
|
Configuration
Installer reference guide
133
ERLA EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1A – 2020.05
#
Code
Description
N/A
[5-05]
Limit DI1
0 A~50 A, step 1 A
N/A
[5-06]
Limit DI2
0 A~50 A, step 1 A
N/A
[5-07]
Limit DI3
0 A~50 A, step 1 A
N/A
[5-08]
Limit DI4
0 A~50 A, step 1 A
kW limits for DI
: Only applicable in case of power limitation mode based on
digital inputs and based on power values.
N/A
[5-09]
Limit DI1
0 kW~20 kW, step 0.5 kW
N/A
[5-0A]
Limit DI2
0 kW~20 kW, step 0.5 kW
N/A
[5-0B]
Limit DI3
0 kW~20 kW, step 0.5 kW
N/A
[5-0C]
Limit DI4
0 kW~20 kW, step 0.5 kW
Average timer
The average timer corrects the influence of ambient temperature variations. The
weather-dependent set point calculation is done on the average outdoor
temperature.
The outdoor temperature is averaged over the selected time period.
#
Code
Description
[A.6.4]
[1-0A]
Outdoor average timer:
▪
0: No averaging
▪
1: 12 hours
▪
2: 24 hours
▪
3: 48 hours
▪
4: 72 hours
Ext. amb. sensor offset.
ONLY applicable in case of an external outdoor ambient sensor is connected and
configured.
You can calibrate the external outdoor ambient temperature sensor. It is possible
to give an offset to the thermistor value. The setting can be used to compensate
for situations where the external outdoor ambient sensor cannot be installed on
the ideal installation location (see installation).
Summary of Contents for ERLA03DAV3
Page 1: ...Installer reference guide Daikin Altherma 3 R F ERLA03DAV3 EHFZ03S18DJ3V...
Page 182: ...1 7 Field settings table 6 8 2 ID9E51 Applicable units EHFZ03S18DJ3V Notes 4P596829 1 2019 10...
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ...4P596821 1A 2020 05 Copyright 2019 Daikin Verantwortung f r Energie und Umwelt...