8
|
Electrical installation
Installer reference guide
76
ERLA EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1A – 2020.05
(a)
MCA=Minimum circuit ampacity. Stated values are maximum values (see electrical data of
combination with indoor units for exact values).
8.1.4 About electrical compliance
Only for ERLA03DAV3
Equipment complying with EN/IEC 61000‑3‑2 (European/International Technical
Standard setting the limits for harmonic currents produced by equipment
connected to public low-voltage systems with input current ≤16 A per phase.).
Only for the backup heater of the indoor unit
"8.3.2 To connect the backup heater power supply"
82].
8.1.5 About preferential kWh rate power supply
Electricity companies throughout the world work hard to provide reliable electric
service at competitive prices and are often authorized to bill clients at benefit
rates. E.g. time-of-use rates, seasonal rates, Wärmepumpentarif in Germany and
Austria, ...
This equipment allows for connection to such preferential kWh rate power supply
delivery systems.
Consult with the electricity company acting as provider at the site where this
equipment is to be installed to know whether it is appropriate to connect the
equipment in one of the preferential kWh rate power supply delivery systems
available, if any.
When the equipment is connected to such preferential kWh rate power supply, the
electricity company is allowed to:
▪
interrupt power supply to the equipment for certain periods of time;
▪
demand that the equipment only consumes a limited amount of electricity during
certain periods of time.
The indoor unit is designed to receive an input signal by which the unit switches
into forced off mode. At that moment, the outdoor unit compressor will not
operate.
The wiring to the unit is different depending on whether the power supply is
interrupted or not.
Summary of Contents for ERLA03DAV3
Page 1: ...Installer reference guide Daikin Altherma 3 R F ERLA03DAV3 EHFZ03S18DJ3V...
Page 182: ...1 7 Field settings table 6 8 2 ID9E51 Applicable units EHFZ03S18DJ3V Notes 4P596829 1 2019 10...
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ...4P596821 1A 2020 05 Copyright 2019 Daikin Verantwortung f r Energie und Umwelt...