9
|
Configuration
Installer reference guide
123
ERLA EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1A – 2020.05
#
Code
Description
[A.4.7]
[0-0E]
[0-0D]
[0-0C]
[0-0B]
Weather-dependent curve
T
DHW
T
a
[0-0C]
[0-0B]
[0-0E]
[0-0D]
▪
T
DHW
: The desired tank temperature.
▪
T
a
:
The
(averaged)
outdoor
ambient
temperature
▪
[0-0E]: low outdoor ambient temperature: –
40°C~5°C
▪
[0-0D]: high outdoor ambient temperature:
10°C~25°C
▪
[0-0C]: desired tank temperature when the
outdoor temperature equals or drops below
the low ambient temperature: 45°C~[6‑0E]°C
▪
[0-0B]: desired tank temperature when the
outdoor temperature equals or rises above the
high ambient temperature: 35°C~[6‑0E]°C
Also see
112] for more information about
weather-dependent curves.
Heat pump operation
#
Code
Description
N/A
[6-00]
The temperature difference determining the heat
pump ON temperature.
2°C~40°C
N/A
[6-01]
The temperature difference determining the heat
pump OFF temperature.
0°C~10°C
Example:
setpoint (T
U
)>maximum heat pump temperature–[6‑01]
t
T
DHW
T
HP ON
T
HP OFF
T
HP MAX
T
U
=
T
BUH OFF
[6-01]
[6-00]
T
U
= 60°C
T
HP MAX
= 50°C
[6-01] = 2°C
[6-00] = 2°C
HP
BUH
HP
5
10
20
30
40
46
48
50
60
HP
Heat pump. If heating up time by the heat pump takes too long, auxiliary heating by the backup heater can
take place.
BUH
Backup heater
Summary of Contents for ERLA03DAV3
Page 1: ...Installer reference guide Daikin Altherma 3 R F ERLA03DAV3 EHFZ03S18DJ3V...
Page 182: ...1 7 Field settings table 6 8 2 ID9E51 Applicable units EHFZ03S18DJ3V Notes 4P596829 1 2019 10...
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ...4P596821 1A 2020 05 Copyright 2019 Daikin Verantwortung f r Energie und Umwelt...