NOTICE
If
Emergency
is set to
Manual
([A.6.C]=0), and the unit is triggered to start
emergency operation, the user interface will ask confirmation before starting. Room
frost protection is active even if the user does NOT confirm emergency operation.
[C‑07]=1: external room thermostat control
Under external room thermostat control, room frost protection is guaranteed by
the external room thermostat, provided that the leaving water temperature home
page is ON on the user interface, and the auto emergency setting ([A.6.C]) is set to
"1".
Additionally, limited frost protection by the unit is possible:
In case of…
…then the following applies:
One leaving water temperature zone
▪
When the leaving water temperature
home page is OFF and the outdoor
ambient temperature drops below
4°C, then the unit will supply leaving
water to the heat emitters to heat up
the room again, and the leaving water
temperature setpoint will be lowered.
▪
When the leaving water temperature
home page is ON, the external room
thermostat is "Thermo OFF" and the
outdoor ambient temperature drops
below 4°C, then the unit will supply
leaving water to the heat emitters to
heat up the room again and the
leaving water temperature setpoint
will be lowered.
▪
When the leaving water temperature
home page is ON and the external
room thermostat is "Thermo ON",
then room frost protection is
guaranteed by the normal logic.
Summary of Contents for ERLA03DAV3
Page 1: ...Installer reference guide Daikin Altherma 3 R F ERLA03DAV3 EHFZ03S18DJ3V...
Page 182: ...1 7 Field settings table 6 8 2 ID9E51 Applicable units EHFZ03S18DJ3V Notes 4P596829 1 2019 10...
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ...4P596821 1A 2020 05 Copyright 2019 Daikin Verantwortung f r Energie und Umwelt...