6/7
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
A.8
[8-02]
R/W
0~10 hour, step: 0,5 hour
0,5 hour
A.8
[8-03]
50
A.8
[8-04]
95
A.8
[8-05]
R/W
0: No
1: Yes
A.8
[8-06]
R/W
0~10°C, step: 1°C
5°C
A.8
[8-07]
R/W
[9-03]~[9-02], step: 1°C
18°C
A.8
[8-08]
R/W
[9-03]~[9-02], step: 1°C
20°C
A.8
[8-09]
R/W
[9-01]~[9-00]°C, step: 1°C
35°C
A.8
[8-0A]
R/W
[9-01]~[9-00]°C, step: 1°C
33°C
A.8
[8-0B]
13
A.8
[8-0C]
10
A.8
[8-0D]
16
A.8
[8-0E]
R/W
-15~25°C, step: 1°C
-7
°C
A.8
[9-00]
R/W
37~60°C, step: 1°C
55°C
A.8
[9-01]
R/W
15~37°C, step: 1°C
25°C
A.8
[9-02]
R/W
18~22°C, step: 1°C
22°C
A.8
[9-03]
R/W
5~18°C, step: 1°C
5°C
A.8
[9-04]
R/W
1~4°C, step: 1°C
1°C
A.8
[9-05]
R/W
15~37°C, step: 1°C
25°C
A.8
[9-06]
R/W
37~55, step: 1°C
55°C
A.8
[9-07]
R/W
5~18°C, step: 1°C
5°C
A.8
[9-08]
R/W
18~22°C, step: 1°C
22°C
A.8
[9-0C]
R/W
1~6°C, step: 0,5°C
1 °C
A.8
[9-0D]
R/W
0~8, step:1
0 : No limitation
1~4 : 50~80%
5~8 : 50~80% during sampling
6
A.8
[9-0E]
R/W
0~8, step:1
0 : No limitation
1~4 : 50~80%
5~8 : 50~80% during sampling
6
A.8
[C-00]
0
A.8
[C-01]
0
A.8
[C-02]
R/W
0: No
1: Bivalent
A.8
[C-03]
R/W
-25~25°C, step: 1°C
0°C
A.8
[C-04]
R/W
2~10°C, step 1°C
3°C
A.8
[C-05]
R/W
0: -
1: 1 contact
2: 2 contacts
A.8
[C-06]
R/W
0: -
1: 1 contact
2: 2 contacts
A.8
[C-07]
R/W
0: LWT control
1: Ext RT control
2: RT control
A.8
[C-08]
R/W
0: No
1: Outdoor sensor
2: Room sensor
A.8
[C-09]
R/W
0: Normally open
1: Normally closed
A.8
[C-0A]
0
A.8
[C-0C]
0
A.8
[C-0D]
0
A.8
[C-0E]
0
A.8
[D-00]
R/W
0: None
1: -
2: BUH only
3: -
A.8
[D-01]
R/W
0: No
1: Active open
2: Active closed
3: Safety thermostat
A.8
[D-02]
R/W
0: No
1: Secondary rtrn
2: Disinf. Shunt
A.8
[D-03]
R/W
0: No
1: increase 2°C, span 4°C
2: increase 4°C, span 4°C
3: increase 2°C, span 8°C
4: increase 4°C, span 8°C
A.8
[D-04]
R/W
0: No
1: Pwr consmp ctrl
A.8
[D-05]
R/W
0: Forced off
1: As normal
A.8
[D-07]
R/W
0: No
1: Yes
A.8
[D-08]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
Is a solar kit connected?
Contact type of preferential kWh rate PS installation?
Which type of DHW pump is installed?
Leaving water temperature compensation around 0°C.
Is a demand PCB connected?
Is the pump allowed to run if prefer. kWh rate PS is cut?
Is an external kWh meter used for power measurement?
What is the required alarm output contact type?
--
--
--
--
Which heaters are permitted if prefer. kWh rate PS is cut?
Bivalent activation temperature.
Bivalent hysteresis temperature.
What is the thermo request contact type for the main zone?
What is the thermo request contact type for the add. zone?
What is the unit control method in space operation?
Which type of external sensor is installed?
Room temperature hysteresis.
Pump speed limitation
Pump speed limitation additional Zone
--
--
Is an external backup heat source connected?
What is the mimimum desired LWT for main zone in cooling? (*)
Leaving water temperature overshoot temperature.
What is the mimimum desired LWT for add. zone in heating?
What is the maximum desired LWT for add. zone in heating?
What is the mimimum desired LWT for add. zone in cooling? (*)
What is the maximum desired LWT for add. zone in cooling? (*)
--
--
What is the ambient temp for BUH only operation?
What is the maximum desired LWT for main zone in heating?
What is the mimimum desired LWT for main zone in heating?
What is the maximum desired LWT for main zone in cooling? (*)
Leaving water temperature maximum modulation.
What is the desired comfort main LWT in cooling? (*)
What is the desired eco main LWT in cooling? (*)
What is the desired comfort main LWT in heating?
What is the desired eco main LWT in heating?
--
Anti-recycling time.
--
--
Allow modulation of the LWT to control the room temp?
4P596829-1 - 2019.10
(*) Setting is not applicable for this unit
Summary of Contents for ERLA03DAV3
Page 1: ...Installer reference guide Daikin Altherma 3 R F ERLA03DAV3 EHFZ03S18DJ3V...
Page 182: ...1 7 Field settings table 6 8 2 ID9E51 Applicable units EHFZ03S18DJ3V Notes 4P596829 1 2019 10...
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ...4P596821 1A 2020 05 Copyright 2019 Daikin Verantwortung f r Energie und Umwelt...